234803
<location>VSM: Memory test
Message value:
-
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, SIC_COMBI, SIC_SINUMERIK_828
Reaction:
OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY
Cause:
An error has occurred during the memory test on the Voltage Sensing Module.
Remedy:
- check whether the permissible ambient temperature for the Voltage Sensing Module is being maintained.
- replace the Voltage Sensing Module.
234804
<location>VSM: CRC
Message value:
%1
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, SIC_COMBI, SIC_SINUMERIK_828
Reaction:
OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY
Cause:
A checksum error has occurred when reading-out the program memory on the Voltage Sensing Module (VSM).
Remedy:
- check whether the permissible ambient temperature for the component is maintained.
- replace the Voltage Sensing Module.
234805
<location>VSM: EPROM checksum error
Message value:
%1
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, SIC_COMBI, SIC_SINUMERIK_828
Reaction:
OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY
Cause:
Internal parameter data is corrupted.
Fault value (r0949, interpret hexadecimal):
01: EEPROM access error.
02: Too many blocks in the EEPROM.
Remedy:
- check whether the permissible ambient temperature for the component is maintained.
- replace the Voltage Sensing Module (VSM).
234806
<location>VSM: Initialization
Message value:
-
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, SIC_COMBI, SIC_SINUMERIK_828
Reaction:
OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY
Cause:
For the Voltage Sensing Module (VSM), a fault has occurred while initializing.
Remedy:
Replace the Voltage Sensing Module.
838
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
Alarms