20203
[Channel %1: ] No active tool
Parameters:
%1 = Channel number
Definitions:
A tool fine compensation has been written for the active tool of channel %1 with PUTFTOC. No tool is active in this
channel. Therefore, the compensation cannot be assigned.
Reaction:
Interpreter stop
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
Correct the program.
Program
Clear alarm with the RESET key. Restart part program
Continuation:
20204
[Channel %1: ] PUTFTOC command not allowed with FTOCOF
Parameters:
%1 = Channel number
Definitions:
A tool fine compensation has been written for channel %1 with PUTFTOC. The tool fine compensation is not active in
this channel. FTOCON must be active in the target channel of the PUTFTOC command.
Reaction:
Interpreter stop
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
Correct the program in the machining channel: Select FTOCON so that the channel is ready to receive the PUTFTOC
command.
Program
Clear alarm with the RESET key. Restart part program
Continuation:
20300
[Channel %1: ] Axis %2 orientation not possible
Parameters:
%1 = Channel number
%2 = Axis name, spindle number
Definitions:
On traversing the displayed (virtual) orientation axis, a tool orientation is to be set
for which the kinematics of this machine are not possible.
Reaction:
Alarm display.
Remedy:
Cancel the JOG movement and specify another (possible) change of orientation.
Program
Alarm display showing cause of alarm disappears. No further operator action necessary.
Continuation:
21550
[Channel %1: ] Axis %2 Travel from hardware limit switch not possible. Reason: %3
Parameters:
%1 = Channel number
%2 = Axis name
%3 = Cause
Definitions:
It has been tried to retract a following axis of an axis coupling or an output axis of a transformation through the master
axis or input axis of a transformation. This is not permitted in the current situation.
Possible reasons:
1 No permissible direction of retraction
2 Coupling not synchronous
3 Retraction not permitted for the active coupling
4 Reserved
5 Retraction not permitted for the active transformation
Alarms
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
NCK alarms
317