6.4.3 Configuration with the ID-Switch

6.4.4 Connect DC 24 V power supply

A6V11940317_en--_a
The ID-Switch must be set to the correct values to identify the components on the
'PACE-Bus' (RS485). The ID must be unique on one 'PACE-Bus' (RS485).
The ID switch 7 and 8 are used to set the RS485 address.
7
8
ID
0
0
10
0
1
11
1
0
12
1
1
13

Table 46: PCIO2001-A1 set the RS485 address with ID switches

0 = OFF; no jumper is set
1 = ON; jumper is set
ID-Switch 1 to 3 settings:
Switch
Function
1
Analog control inputs are used as supervised inputs
2
Analog inputs are used to supervise relay outputs
3
Logic control inputs 1 to 8 are used as relay controls

Table 47: PCIO2001-A1 function settings with ID switches

The ID-switch 4 to 6 are reserved for future application and should stay in the
OFF position.
The PCIO2001-A1 provides two DC 24 V power supply connectors ('X1' and 'X6')
DC 24 V power supply connectors - 'X1' and 'X6'
Pin
Description
1
DC 24 V
2
DC 0 V

Table 48: PCIO2001-A1 DC 24 V power supply connectors - 'X1' and 'X6'

Install internal components
Input/Output extension (digital 16) PCIO2001-A1
Remark
Power supply
Power supply
6