Siemens G130 List Manual page 1458

Hide thumbs Also See for G130:
Table of Contents

Advertisement

4 Faults and alarms
4.2 List of faults and alarms
F01690
SI Motion: Data save problem for the NVRAM
Message value:
%1
Message class:
Hardware/software error (1)
Drive object:
All objects
Component:
Control Unit (CU)
Reaction:
Vector: NONE (OFF1, OFF2, OFF3)
Infeed: NONE (OFF1, OFF2)
Acknowledge:
POWER ON
Cause:
There is not sufficient memory space in the NVRAM on the drive to save parameters r9781 and r9782 (safety
logbook).
Note:
This fault does not result in a safety stop response.
Fault value (r0949, interpret decimal):
0: There is no physical NVRAM available in the drive.
1: There is no longer any free memory space in the NVRAM.
Remedy:
For fault value = 0:
- use a Control Unit NVRAM.
For fault value = 1:
- deselect functions that are not required and that take up memory space in the NVRAM.
- contact Technical Support.
Note:
NVRAM: Non-Volatile Random Access Memory (non-volatile read and write memory)
A01691 (F)
SI Motion: Ti and To unsuitable for DP cycle
Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Component:
None
Reaction:
NONE
Acknowledge:
NONE
Cause:
The configured times for PROFIBUS communication are not permitted and the DP cycle is used as the actual value
acquisition cycle for the safe movement monitoring functions.
Isochronous PROFIBUS:
The sum of Ti and To is too high for the selected DP cycle. The DP cycle should be at least 1 current controller cycle
greater than the sum of Ti and To.
No isochronous PROFIBUS:
The DP clock cycle must be at least 4x the current controller clock cycle.
Notice:
If this alarm is not observed, then message C01711 or C30711 – with the value 1020 ... 1021 – can sporadically
occur.
Remedy:
Configure Ti and To low so that they are suitable for the DP cycle or increase the DP cycle time.
Alternative when SI monitoring integrated in the drive is enabled (p9601/p9801 > 0):
Use the actual value acquisition cycle p9511/p9311 and, in turn, set independently from DP cycle. The actual values
sensing clock cycle must be at least 4x the current controller clock cycle. A clock cycle ratio of at least 8:1 is
recommended.
See also: p9511 (SI Motion actual value sensing cycle clock (Control Unit))
Reaction upon F:
NONE (OFF1, OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY (POWER ON)
1458
Propagation:
LOCAL
Propagation:
GLOBAL
List Manual (LH2), 07/2016, A5E03263479A
SINAMICS G130/G150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents