Test And Measuring Equipment - Siemens FC700A Maintenance Instructions Manual

Fire detection system
Table of Contents

Advertisement

Test and measuring equipment

3
Test and measuring equipment
10
Siemens Building Technologies
Fire & Security Products
Multimeter
Accuracy ≤ 2%
Internal resistance ≥ 20kΩ
Measuring ranges 1 to 500VAC / DC, 100mA to 5ADC, 10Ω to10MΩ
Battery test set
Load resistor 5Ω
Maintenance-PC
System requirements see document 007895
Detector tester
Depending on detector type / detector system
For all detectors OP620, OH620 and HI62x
Detector exchanger DZ1191
Detector exchanger and tester DZ1193
For smoke detectors OP... and OH...
Detector tester RE6 and test gas
For heat detectors HI...
Detector tester RE6T
For smoke detectors DLO1191
Detector tester RE10
Adjustment set DZL1191
For flame detectors DF1191/92
Test lamp LE3, StabexHF for explosion hazard areas
Line tester
Depending on detector type
For collective detector lines
Alarm test probe (5.6V Zener diode with 220Ω resistor)
For addressable detector lines
Line test unit DZ1131