14.5

List of Error Codes

Simple Motion module detection error

Error code
Error name
(Hexadecimal)
0000H
Normal
1080H
Flash ROM write
number error
1867H
Dedicated instruction
I/F error
18B0H
Error when switching
from normal
operation mode to
amplifier-less
operation mode
18B1H
Error when switching
from amplifier-less
operation mode to
normal operation
mode
18C0H
Unit synchronization
cycle setting
unsupported
1900H
PLC READY OFF
during operation
1902H
Servo READY signal
OFF during
operation
1903H
Test mode faults
during operation
1904H
Hardware stroke limit
(+)
Error details and causes
Data is written to the flash ROM continuously 25 times
or more from the program.
[Operation status at error occurrence]
The system does not write data to the flash ROM.
Mismatching occurs between the CPU module and the
Simple Motion module.
[Operation status at error occurrence]
At start: The system does not operate.
Input signals other than synchronization flag [X1] are
ON when switching from the normal operation mode to
the amplifier-less operation mode.
[Operation status at error occurrence]
The operation mode is not changed.
Input signals other than synchronization flag [X1] are
ON when switching from the amplifier-less operation
mode to the normal operation mode.
[Operation status at error occurrence]
The operation mode is not changed.
The setting value of unit synchronization cycle is
unsupported.
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
The PLC READY signal [Y0] is turned OFF during
operation.
[Operation status at error occurrence]
The system stops with the setting (deceleration stop/
sudden stop) of the detailed parameter 2 Sudden stop
selection (stop group 2).
(Note that the deceleration stop only occurs during the
manual pulse generator operation.)
The servo READY signal is turned OFF during
operation.
[Operation status at error occurrence]
During operation: The system stops immediately.
The personal computer cannot communicate with the
CPU module.
[Operation status at error occurrence]
The system stops with the setting (deceleration stop/
sudden stop) of the detailed parameter 2 Sudden stop
selection (stop group 2).
(Note that the deceleration stop only occurs during the
manual pulse generator operation.)
Start is requested when the hardware stroke limit (upper
limit signal FLS) is turned OFF.
[Operation status at error occurrence]
The system does not start.
Remedy
Review the program so that data is not written
continuously to the flash ROM. (Using "[Md.19]", the
number of flash ROM write times can be monitored.)
(If this error has occurred in a proper using method,
writing is enabled by resetting the error, switching
power OFF, then ON, or resetting the CPU module.)
A trouble occurs. Repair.
Switch the operation mode after confirming that all
input signals other than synchronization flag [X1] are
OFF.
Switch the operation mode after confirming that all
input signals other than synchronization flag [X1] are
OFF.
With the setting brought into the supported range,
switch the power on again or reset the CPU module.
Review the program which turns ON/OFF PLC READY
signal [Y0].
Check the servo amplifier power, wiring with the servo
amplifier, and connection of connectors.
Check that there is no error on the personal computer
side I/F to which a cable is connected.
• Check the wiring of upper limit signal FLS.
• Check if the specification of the limit switch and the
setting of the "[Pr.22] Input signal logic selection"
match.
• If hardware stroke limit (limit switch) is unnecessary
system for installation, wire to always turn ON the
upper limit signal (FLS) input of the Simple Motion
module.
14 TROUBLESHOOTING
14.5 List of Error Codes
14
591