JOG operation execution procedure

The JOG operation is carried out by the following procedure.
Preparation
JOG operation
start
Monitoring of the
JOG operation
JOG operation
stop
• Mechanical elements such as limit switches are considered as already installed.
• Parameter settings work in common for all control using the Simple Motion module.
5 MANUAL CONTROL
168
5.2 JOG Operation
STEP 1
Create a program for the following setting.
STEP 2
Set a "0" in "[Cd.16] Inching movement amount".
Set the "[Cd.17] JOG speed". (Control data setting)
Create a program in which the "JOG start signal" is
turned ON by a JOG operation start command.
STEP 3
Write the program created in STEP1
and STEP2 to the CPU module.
STEP 4
Turn ON the JOG start signal of the axis to be started.
STEP 5
Monitor the JOG operation status.
STEP 6
Turn OFF the JOG start signal that is ON.
End of control
Set the parameters.
([Pr.1] to [Pr.39])
One of the following two methods can be used.
<Method 1>
Directly set (write) the parameters in
the Simple Motion module using
the engineering tool.
<Method 2>
Set (write) the parameters from
the CPU module to the Simple Motion module
using the program.
Turn ON the JOG start signal.
[Cd.181] Forward run JOG start
[Cd.182] Reverse run JOG start
Monitor using the engineering tool.
Stop the JOG operation when the JOG start signal
is turned OFF using the program in STEP 2.