Chapter 6 Control Modes of Operation

6.2.2 Command Source of Position (PR) Control Mode

The command sources of PR mode are (P6-00, P6-01) ~ (P7-26, P7-27) these 64 built-in
parameters. Using with external I/O signals (CN1, POS 0 to POS 5 and CTRG) can select
one of the 64 built-in parameters to be position command. Please refer to the table below:
Position
POS5
Command
P1
ON
P2
ON
~
P50
OFF
P51
OFF
~
P64
OFF
State of POS0~5: 0 indicates the contact is OFF (Normally Open)
1 indicates the contact is ON (Normally Closed)
CTRG : the instant time when the contact changes from 0 (open) to 1 (closed).
The application of absolute and incremental position control is various and multiple. This
kind of position control is equal to a simple sequence control. Users can easily complete
the cycle running by using the above table. For example, the position command, P1 is 10
turns and P2 is 20 turns. Give the position command P1 first and then give the position
command P2. The difference between absolute and incremental position control is shown
as the figure below:
Absolute Type
6-8
POS4
POS3
POS2
ON
ON
ON
ON
ON
ON
OFF
ON
ON
OFF
ON
ON
OFF
OFF
OFF
20 turns
10 turns
POS1
POS0
CTRG
ON
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
Incremental Type
10 turns
Parameters
P6-00
P6-01
P6-02
P6-03
~
P6-98
P6-99
P7-00
P7-01
~
P7-26
P7-27
20 turns
Revision September 2012