Timing chart for using servo motor with electromagnetic brake:
SON
OFF
(DI Input)
BRKR
OFF
(DO Output)
Motor Speed
BRKR output timing explanation:
1. When Servo Off (when DI SON is not activated), the BRKR output goes Off
(electromagnetic brake is locked) after the delay time set by P1-43 is reached and
the motor speed is still higher than the setting value of P1-38.
2. When Servo Off (when DI SON is not activated), the BRKR output goes Off
(electromagnetic brake is locked) if the delay time set by P1-43 is not reached and
the motor speed is still lower than the setting value of P1-38.
Electromagnetic Brake Wiring Diagram
NOTE
1)
Please refer to Chapter 3 Connections and Wiring for more wiring information.
2)
The BRKR signal is used to control the brake operation. The VDD DC24V power supply
of the servo drive can be used to power the relay coil (Relay). When BRKR signal is ON,
the motor brake will be activated.
3)
Please note that the coil of brake has no polarity.
4)
The power supply for brake is DC24V. Never use it for VDD, the +24V source voltage.
Revision September 2012
ON
ON
MBT1(P1-42)
Chapter 6 Control Modes of Operation
OFF
OFF
MBT2(P1-43)
ZSPD(P1-38)
6-63