Delta ASDA-A2 Series User Manual page 442

High resolution ac servo drive for network communication applications
Hide thumbs Also See for ASDA-A2 Series:
Table of Contents

Advertisement

A2
ASDA-
P4-10
CEN
Operation
Interface:
Default: 0
Control
Mode:
Range: 0 ~ 6
Data Size: 16-bit
Display
Format:
Settings:
0: Reserved
1: Execute analog speed input drift adjustment
2: Execute analog torque input drift adjustment
3: Execute current detector (V phase) drift adjustment
4: Execute current detector (W phase) drift adjustment
5: Execute drift adjustment of the above 1~4
6: Execute IGBT NTC calibration
Please note:
1. This adjustment function is enabled after parameter P2-08 is set to 20.
2. When executing any adjustment, the external wiring connected to analog
speed or torque must be removed and the servo system should be off (Servo
off).
P4-11
SOF1
Operation
Interface:
Default: Factory setting
Control
Mode:
Range: 0 ~ 32767
Data Size: 16-bit
Display
Format:
Settings:
The adjustment functions from P4-11 through P4-19 are enabled after parameter
P2-08 is set to 22. Although these parameters allow the users to execute manual
adjustment, we still do not recommend the users to change the default setting
value of these parameters (P4-11 ~ P4-19) manually.
Please note that when P2-08 is set to 10, the users cannot reset this parameter.
Revision September 2012
Adjustment Function
Keypad / Software
ALL
Unit: N/A
Decimal
Analog Speed Input Drift Adjustment 1
Keypad / Software
ALL
Unit: N/A
Decimal
Chapter 8 Servo Parameters
Communication
Communication
Address: 0414H
0415H
Related Section: N/A
Address: 0416H
0417H
Related Section: N/A
8-165