4 Faults and alarms
4.2 List of faults and alarms
F05059
Parallel circuit: VSM firmware versions differ
Message value:
Parameter: %1
Message class:
General drive fault (19)
Drive object:
B_INF, VECTOR_G
Component:
Power Module
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The firmware versions of the Voltage Sensing Module (VSM) do not match.
Fault value (r0949, interpret decimal):
Parameter in which the first different version number was detected.
Remedy:
For parallel circuit configurations, only Voltage Sensing Modules (VSM) with identical firmware versions may be
used.
F05060
Parallel circuit: Power unit firmware version does not match
Message value:
Parameter: %1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
B_INF, VECTOR_G
Component:
Power Module
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
Firmware from version V02.30.01.00 is required when connecting the power units in parallel.
Remedy:
Update the firmware of the power units (at least V02.30.01.00).
F05061
Infeed VSM count
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
B_INF, VECTOR_G
Component:
Voltage Sensing Module (VSM)
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The number of active Voltage Sensing Modules (VSM) for the drive object infeed with chassis power units is not
correct.
For A_Infeed, each active power unit must be assigned an active VSM also for a parallel circuit configuration.
For S_Infeed, the active drive object, must be assigned at least one active VSM.
Fault value (r0949, interpret decimal):
Number of VSMs that are currently assigned to the drive object.
Remedy:
Adapts the number of active Voltage Sensing Modules (VSM).
F05064
Parallel connection: Pulse synchronization error
Message value:
-
Message class:
General drive fault (19)
Drive object:
VECTOR_G
Component:
Power Module
Reaction:
OFF2 (OFF1, OFF3)
Acknowledge:
POWER ON (IMMEDIATELY)
Cause:
The pulse synchronization of at least one of the power units connected in parallel is incorrect.
Remedy:
Restart the drive system.
1524
Propagation:
GLOBAL
Propagation:
GLOBAL
Propagation:
GLOBAL
Propagation:
GLOBAL