Fault value (r0949, interpret decimal):
Parameter in which the inadmissible power unit code number was detected.
Remedy:
- Use power units with the same code number.
For booksize drive units, the following additionally applies:
- use power units which are permitted for a parallel connection.
- reduce the number of power units being used in the parallel connection.
F05056
Parallel circuit: Power unit EEPROM versions differ
Message value:
Parameter: %1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
B_INF, VECTOR_G
Component:
Power Module
Reaction:
OFF2 (NONE)
Acknowledge:
IMMEDIATELY
Cause:
The EEPROM versions of the power units do not match.
Fault value (r0949, interpret decimal):
Parameter in which the first different version number was detected.
Remedy:
Use power units with the same EEPROM version.
Note:
For parallel circuit configurations, only power units with identical EEPROM versions may be used.
F05057
Parallel circuit: Power unit firmware versions differ
Message value:
Parameter: %1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
B_INF, VECTOR_G
Component:
Power Module
Reaction:
OFF2 (NONE)
Acknowledge:
IMMEDIATELY
Cause:
The firmware versions of the power units connected in parallel do not match.
Fault value (r0949, interpret decimal):
Parameter in which the first different version number was detected.
Remedy:
Use power units with the same firmware version.
For parallel circuit configurations, only power units with identical firmware versions may be used.
F05058
Parallel circuit: VSM EEPROM versions differ
Message value:
Parameter: %1
Message class:
General drive fault (19)
Drive object:
B_INF, VECTOR_G
Component:
Power Module
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The EEPROM versions of the Voltage Sensing Modules (VSM) do not match.
Fault value (r0949, interpret decimal):
Parameter in which the first different version number was detected.
Remedy:
For parallel circuit configurations, only Voltage Sensing Modules (VSM) with identical EEPROM versions may be
used.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Propagation:
GLOBAL
Propagation:
GLOBAL
Propagation:
GLOBAL
4 Faults and alarms
4.2 List of faults and alarms
1523