F06310 (A)
Supply voltage (p0210) incorrectly parameterized
Message value:
-
Message class:
Network fault (2)
Drive object:
VECTOR_G
Component:
None
Reaction:
NONE (OFF1, OFF2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
For AC/AC drive units, the measured DC voltage lies outside the tolerance range after precharging has been
completed.
The following applies for the tolerance range: 1.16 * p0210 < r0070 < 1.6 * p0210
Note:
The fault can only be acknowledged when the drive is switched off.
See also: p0210 (Drive unit line supply voltage)
Remedy:
- check the parameterized supply voltage and if required change (p0210).
- check the line supply voltage.
See also: p0210 (Drive unit line supply voltage)
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F06310 (A)
Infeed: Supply voltage (p0210) incorrectly parameterized
Message value:
Line supply voltage: %1
Message class:
Network fault (2)
Drive object:
B_INF
Component:
None
Reaction:
NONE (OFF1, OFF2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
After precharging was completed, the line supply voltage Vrms was calculated using the measured DC link voltage.
This voltage Vrms is not within the tolerance range of the supply voltage.
The following applies for the tolerance range: 85 % * p0210 < Vrms < 110 % * p0210
Fault value (r0949, floating point):
Line supply voltage Vrms present.
See also: p0210 (Drive unit line supply voltage)
Remedy:
- check the parameterized supply voltage and if required change (p0210).
- check the line supply voltage.
See also: p0210 (Drive unit line supply voltage)
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F06311
Infeed: Supply voltage (p0210) incorrect
Message value:
Line supply voltage: %1
Message class:
Network fault (2)
Drive object:
B_INF
Component:
None
Reaction:
OFF2 (OFF1)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The line voltage nominal value indicated in p0210 is outside the nominal voltage range of the power unit.
After precharging was completed, the actual line supply voltage Vrms was calculated using the measured DC link
voltage. This voltage Vrms does not lie within the extended tolerance range of the supply voltage set in p0210.
The following applies for the extended tolerance range: 75 % * p0210 < Vrms < 120 % * p0210
Alarm value (r2124, floating point):
Line supply voltage Vrms present.
See also: p0210 (Drive unit line supply voltage)
Remedy:
- check the parameterized supply voltage and if required change (p0210).
- check the line supply voltage.
See also: p0210 (Drive unit line supply voltage)
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Propagation:
GLOBAL
Propagation:
GLOBAL
Propagation:
GLOBAL
4 Faults and alarms
4.2 List of faults and alarms
1529