A07089
Changing over units: Function module activation is blocked because the units have
been changed over
Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Component:
None
Reaction:
NONE
Acknowledge:
NONE
Cause:
An attempt was made to activate a function module. This is not permissible if the units have already been changed
over.
See also: p0100 (IEC/NEMA mot stds), p0349 (System of units motor equivalent circuit diagram data), p0505
(Selecting the system of units)
Remedy:
Restore units that have been changed over to the factory setting.
A07092
Drive: moment of inertia estimator still not ready
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Component:
Control Unit (CU)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The moment of inertia estimator has still not determined any valid values.
The acceleration cannot be calculated.
The moment of inertia estimator has stabilized, if the frictional values (p1563, p1564) as well as the moment of inertia
value (p1493) have been determined and the appropriate status signal is set (r1407.26 = 1).
The following parameters influence the response of the moment of the inertia estimator:
p1560, p1561, p1562
Remedy:
Traverse the axis until the moment of inertia estimator has stabilized.
This alarm is automatically withdrawn after the moment of inertia estimator has stabilized.
A07094
General parameter limit violation
Message value:
Parameter: %1
Message class:
Hardware/software error (1)
Drive object:
All objects
Component:
None
Reaction:
NONE
Acknowledge:
NONE
Cause:
As a result of the violation of a parameter limit, the parameter value was automatically corrected.
Minimum limit violated --> parameter is set to the minimum value.
Maximum limit violated --> parameter is set to the maximum value.
Alarm value (r2124, interpret decimal):
Parameter number, whose value had to be adapted.
Remedy:
Check the adapted parameter values and if required correct.
F07100
Drive: Sampling times cannot be reset
Message value:
Parameter: %1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
B_INF, VECTOR_G
Component:
None
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
When resetting drive parameter (p0976) sampling times cannot be reset using p0111, p0112, p0115.
Fault value (r0949, interpret decimal):
Parameter whose setting prevents the sampling times being reset.
See also: r0110 (Basic sampling times)
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Propagation:
LOCAL
Propagation:
GLOBAL
Propagation:
LOCAL
Propagation:
GLOBAL
4 Faults and alarms
4.2 List of faults and alarms
1539