Bi: Cu Signal Source For Terminal Do 0 / Cu S_Src Do 0; Bi: Cu Signal Source For Terminal Do 1 / Cu S_Src Do 1 - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Parameters
7.3 Parameters
p0730

BI: CU signal source for terminal DO 0 / CU S_src DO 0

Access level: 2
Can be changed: T, U
Unit group: -
Min:
-
Description:
Sets the signal source for terminal DO 0 (NO: X134. 19 / NC: X134. 18).
Recommendation:
r0052.0 Ready for switching on
r0052.1 Ready for operation
r0052.2 Operation enabled
r0052.3 Fault present
r0052.4 Coast down active (OFF2)
r0052.5 Quick stop active (OFF3)
r0052.6 Switching on inhibited active
r0052.7 Alarm present
r0052.9 Control request
r0052.14 Motor rotates forwards
r0053.0 DC braking active
r0053.1 n_act > p2167 (n_off)
r0053.2 n_act <= p1080 (n_min)
r0053.3 I_act > p2170
r0053.4 n_act > p2155
r0053.5 n_act <= p2155
r0053.6 n_act >= n_set
r0053.10 Technology controller output at the lower limit
r0053.11 Technology controller output at the upper limit
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note
DO: Digital Output
Relay output: NO = normally open, NC = normally closed
p0731

BI: CU signal source for terminal DO 1 / CU S_src DO 1

Access level: 2
Can be changed: T, U
Unit group: -
Min:
-
Description:
Sets the signal source for terminal DO 1 (NO: X134. 21).
428
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Data type: Unsigned32 / Binary
Dynamic index: -
Function diagram: 2119, 2030,
2130
Factory setting:
52.3
Data type: Unsigned32 / Binary
Dynamic index: -
Function diagram: 2119, 2030,
2130
Factory setting:
52.2
SINAMICS G120XA converter