Functions
9.5 Setpoint preparation
9.5.3

Inhibit direction of rotation

Procedure
In the factory setting of the converter, both motor directions of rotation are enabled.
If you want to permanently inhibit one of the
directions of rotation, then you must set the
corresponding parameter to 1.
With the value 0, the converter enables the
direction of rotation.
Table 9- 23
Parameter
p1110 = 1
p1110 = 722.3
9.5.4

Minimum speed

Function
The inverter prevents continuous motor operation at
speeds < minimum speed.
Speeds, where the absolute value is less than the
minimum speed, can only be passed through when
accelerating or braking.
Table 9- 24
Parameter
p1080
182
Examples of settings to inhibit the direction of rotation
Remark
Inhibit negative direction
Negative direction is permanently inhibited.
Inhibit negative direction
Digital input 3 = 0: Negative direction of rotation is enabled.
Digital input 3 = 1: Negative direction of rotation is inhibited.
Setting the minimum speed
Description
Minimum speed
SINAMICS G120C frequency converter
Operating Instructions, 03/2012, FW V4.5, A5E02999804B AB
p1111
0
p1110
0