Ramp-Function Generator Minimum Ramp-Down Time / Rfg T_Rd Min; Ramp-Function Generator Initial Rounding-Off Time / Rfg T_Start_Round; Ramp-Function Generator Final Rounding-Off Time / Rfg T_End_Delay - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Note
For U/f control and sensorless vector control (see p1300), a ramp-down time of 0 s does not make sense. The setting
should be based on the startup times (r0345) of the motor.
p1127[0...n]

Ramp-function generator minimum ramp-down time / RFG t_RD min

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0.000 [s]
Description:
Sets the minimum ramp-down time.
The ramp-down time (p1121) is limited internally to this minimum value.
The parameter cannot be set shorter than the minimum ramp-up time (p1123).
Dependency:
See also: p1082
Note
For U/f control and sensorless vector control (see p1300), a ramp-down time of 0 s does not make sense. The setting
should be based on the startup times (r0345) of the motor.
If the maximum speed p1082 changes, p1127 is re-calculated.
p1130[0...n]

Ramp-function generator initial rounding-off time / RFG t_start_round

Access level: 2
Can be changed: T, U
Unit group: -
Min:
0.000 [s]
Description:
Sets the initial rounding-off time for the extended ramp generator. The value applies to ramp-up and ramp-down.
Note
Rounding-off times avoid an abrupt response and prevent damage to the mechanical system.
Rounding off is not active if the technology controller is used as main speed setpoint (p2251 = 0).
p1130[0...n]
Ramp-function generator initial rounding-off time / RFG t_start_round
CUG120XA_USS
Access level: 2
(PM330)
Can be changed: T, U
Unit group: -
Min:
0.000 [s]
Description:
Sets the initial rounding-off time for the extended ramp generator. The value applies to ramp-up and ramp-down.
Note
Rounding-off times avoid an abrupt response and prevent damage to the mechanical system.
Rounding off is not active if the technology controller is used as main speed setpoint (p2251 = 0).
p1131[0...n]

Ramp-function generator final rounding-off time / RFG t_end_delay

Access level: 2
Can be changed: T, U
Unit group: -
Min:
0.000 [s]
Description:
Sets the final rounding-off time for the extended ramp generator.
The value applies to ramp-up and ramp-down.
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Calculated: CALC_MOD_ALL Data type: FloatingPoint32
Scaling: -
Unit selection: -
Max:
999999.000 [s]
Calculated: -
Scaling: -
Unit selection: -
Max:
30.000 [s]
Calculated: -
Scaling: -
Unit selection: -
Max:
30.000 [s]
Calculated: -
Scaling: -
Unit selection: -
Max:
30.000 [s]
Parameters
7.3 Parameters
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
0.000 [s]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 3070
Factory setting:
0.000 [s]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 3070
Factory setting:
2.000 [s]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 3070
Factory setting:
0.000 [s]
483