r0231[0...1]

Power cable length maximum / Cable length max

Access level: 3
Can be changed: -
Unit group: -
Min:
- [m]
Description:
Displays the maximum permissible cable lengths between the drive unit and motor.
Index:
[0] = Unshielded
[1] = Shielded
Note
The display value is used to provide information for service and maintenance.
p0233

Power unit motor reactor / PU mot reactor

Access level: 2
Can be changed: C2(1), T, U
Unit group: -
Min:
0.000 [mH]
Description:
Enter the inductance of a filter connected at the power unit output.
Dependency:
This parameter is automatically pre-set when you select a filter via p0230 if a SIEMENS filter is defined for the power
unit.
See also: p0230
Note
When exiting the quick commissioning using p3900 = 1, the parameter value is set to the value of the defined SIEMENS
filter or to zero. For this reason, the parameter value of a third-party filter only has to be entered outside the
commissioning phase (p0010 = 0) and then the controller calculation (p0340 = 3) is carried out.
The parameter cannot be changed if the power unit (e.g. PM260) is equipped with an internal sine-wave filter.
p0234

Power unit sine-wave filter capacitance / PU sine filter C

Access level: 2
Can be changed: C2(1), T, U
Unit group: -
Min:
0.000 [µF]
Description:
Enters the capacitance of a sine-wave filter connected at the power unit output.
Dependency:
This parameter is automatically pre-set when you select a filter via p0230 if a SIEMENS filter is defined for the power
unit.
See also: p0230
Note
The parameter value includes the sum of all of the capacitances of a phase connected in series (phase - ground).
When exiting the quick commissioning using p3900 = 1, the parameter value is set to the value of the defined SIEMENS
filter or to zero. For this reason, the parameter value of a third-party filter only has to be entered outside the
commissioning phase (p0010 = 0).
The parameter cannot be changed if the power unit (e.g. PM260) is equipped with an internal sine-wave filter.
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Calculated: -
Scaling: -
Unit selection: -
Max:
- [m]
Calculated: -
Scaling: -
Unit selection: -
Max:
1000.000 [mH]
Calculated: -
Scaling: -
Unit selection: -
Max:
1000.000 [µF]
Parameters
7.3 Parameters
Data type: Unsigned16
Dynamic index: -
Function diagram: -
Factory setting:
- [m]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
0.000 [mH]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
0.000 [µF]