Module Specifications - YASKAWA JEPMC-MP2300-Y Series User Manual

Machine controller basic module
Table of Contents

Advertisement

3.2.3 Module Specifications

( 1 ) Basic Module Hardware Specifications
The following table shows the hardware specifications of the Basic Module.
Item
Classification
Name
Model Number
Flash Memory
SDRAM
SRAM
Motion Network
MECHATROLINK
I/O Signal
Calendar
Connectors
Indicators
Switches
Current Consumption
Dimensions (mm)
Mass
Basic Module
MP2300
JEPMC-MP2300
8 MBytes (User area 5.5 MBytes)
16 MBytes
256 kBytes: M registers, S registers, trace memory, alarm history (battery backup)
Motion network 1 channel
SERVOPACK and I/O for up to 21 stations connectable (SERVOPACK for up to 16
axes)
Baud rate: 4 Mbps (MECHATROLINK-I) or 10 Mbps (MECHATROLINK-II)
8 digital inputs (1 input also used as an interrupt input)
24 VDC, 4.1 mA (TYP) source mode/sink mode inputs
4 digital outputs
24 VDC, 100 mA (TYP) open-collector sink mode outputs
Seconds to year timer
(Battery backup)
POWER: Power supply connector
M-I/II: MECHATROLINK connector
CPU I/O: I/O connector
RDY (green)
RUN (green)
ALM (red)
ERR (red)
TX (green)
BAT (red)
STOP
SUP
INIT
CNFG
MON
TEST
1A max.
120 × 130 × 105 (W × H × D)
450 g
Specifications
3.2 Basic Module
3-9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mp2300

Table of Contents