YASKAWA JEPMC-MP2300-Y Series User Manual page 218

Machine controller basic module
Table of Contents

Advertisement

4 Mounting and Wiring
4.4.2 LIO-04/LIO-05 Module Connections
( 9 ) LIO-05 Module Connector Connection Examples
24 VDC
CN1 connector
+ -
pin No.
Com-
- +
mon 1
1
Input 0
2
Input 1
27
5
Input 6
Input 7
30
DC24V
+ -
Com-
mon 2
- +
6
Input 8
7
32
Input 9
Input 14
10
35
Input 15
4-44
■ CN1 Connector Connection Example
JEPMC-IO2304
+5V
Photocoupler
R
5.6 kΩ
R
Photocoupler
R
Photocoupler
R
Check the polarity of the external power supply when wiring. An adverse connection may cause a
load malfunction.
The pins No. 15 and 40 and the pins No. 22 and 47 are internally connected. Connect them exter-
nally as well.
Fuse blowout
detection circuit
40
R
15
12
37
13
38
16
41
17
42
39
Fuse blowout
detection circuit
47
R
22
19
44
20
45
23
48
24
49
46
24 VDC
+ -
Output 0
L
Output 1
L
Output 2
L
Output 3
L
Output 4
L
Output 5
L
Output 6
L
Output 7
L
24 VDC
+ -
Output 8
L
Output 9
L
Output 10
L
Output 11
L
Output 12
L
Output 13
L
Output 14
L
Output 15
L

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mp2300

Table of Contents