217If-01 Modules - YASKAWA JEPMC-MP2300-Y Series User Manual

Machine controller basic module
Table of Contents

Advertisement

5.5.8 217IF-01 Modules

( 1 ) RS422/485 Interface
Item
Communication protocol
Master/Slave
Device address
Serial interface
Communication mode
Data length
Parity
Stop bits
Baud rate
Transmission delay
Automatic reception
Interface register settings at the
slave
When self-configuration is executed, the following parameter settings will be made for the RS422/
485 interface of 217IF-01 Modules.
MEMOBUS
Slave
1
RS485
RTU
8 bits
Even
1 bit
19.2 Kbps
Disable
Enable
Reading input relays
Reading input registers
Reading/writing coils
Reading/writing holding registers
Writing range for coil holding
registers
Depending on the settings of connected devices, MEMOBUS message communication may be
possible using the automatic reception function.
5.5 Definition Data Refreshed by Self-configuration and Allocation Examples
Setting
Leading Register
IW0000
IW0000
MW00000
MW00000
MW00000
LO: MW00000
HI: MW65534
Number of Words
32,768
32,768
65,535
65,535
5-39