4.4.1 LIO-01/LIO-02 Modules

( 6 ) Output Circuit
Item
Outputs
Output Format
Isolation Method
Output Voltage
Output Current
Leakage Current When
OFF
ON Time/OFF Time
Number of Commons
Protection Circuit
Error Detection
Other Functions
4-30
The following table shows the LIO-01/LIO-02 Module output circuit specifications.
16 points
LIO-01
Transistor, open collector sink mode outputs
LIO-02
Transistor, open collector source mode outputs
Photocoupler
±
+24 VDC,
20%
100 mA max.
0.1 mA max.
ON: 1 ms max.
OFF: 1 ms max.
16 points
Fuse
The fuse is not, however, for circuit protecttion. It is for protecting against fire at output shorts.
Attach a fuse externally to each output if circuit protection is required.
Fuse blown detection
DO_00 is shared with counter position detection.
Output
R
register