( 7 ) Output Circuit
Item
Outputs
32 points
LIO-04
Output Format
LIO-05
Isolation Method
Photocoupler
Output Voltage
+24 VDC (+192 to +28.8 VDC)
Output Current
100 mA max.
Leakage Current
0.1 mA max.
When OFF
ON: 0.5 ms max.
ON Time/OFF Time
OFF: 1 ms max.
Number of Commons
Common ground
Fuse
Protection Circuit
The fuse is not, however, for circuit protection. It is for protecting against fire at output shorts.
Attach a fuse externally to each output if circuit protection is required.
Fuse Rating
1 A
Error Detection
Fuse blowout detection
The following table shows the LIO-04/LIO-05 Module output circuit specifications.
Transistor, sink mode output
Transistor, source mode output
Output
R
register
Fig. 4.11 LIO-04 Digital Output Circuit (Sink Mode Output)
Output
R
register
Fig. 4.12 LIO-05 Digital Output Circuit (Source Mode Output)
Specifications
Photocoupler
R
R
R
Photocoupler
4.4 I/O Module (Optional) Connections
+24V
+24V
DO_OUT
Transistor
0V
0
+24V
+24V
Transistor
DO_OUT
0V
0
24
24
4-41