[ c ] LED Indicators
The following table shows the LIO-04/LIO-05 status when the each indicator lamp is lit or unlit.
RUN
FUSE
( 3 ) Specifications
The hardware specifications and temperature characteristics of LIO-04/LIO-05 Module are as fol-
lows.
[ a ] Hardware Specifications
Item
Classification
Name
Model
Digital Input
Digital Output
LED Indicators
Connectors
Current Consumption
Dimensions (mm)
Mass
Indicator
Color
RUN
Green
Normal operation
One or some of the output protection
FUSE
Red
fuses is blown out.
I/O Module
LIO-04
JAPMC-IO2303
32 inputs
±
24-VDC
20% (+19.2V to +28.8V), 4.1 mA (TYP),
combined sink mode/source mode inputs (DI-00, -01, -16, and -17 also used for interrupts)
Number of simultaneously ON inputs: 16 (8/connector with 24 VDC),
32 outputs
±
24-VDC
20% (+19.2V to +28.8V),
100 mA max.,
transistor outputs, sink mode outputs
RUN (green)
FUSE (red)
CN1: I/O connector
CN2: I/O connector
500mA max.
125 × 95 (H× D)
80 g
Status When Lit
Error occurrence
All the output protection fuses are
normal.
Specifications
LIO-05
JAPMC-IO2304
10 (5/connector with 28.8 VDC)
*For details, refer to [ b ] Number of Simultaneously ON
Inputs - Ambient Temperature Characteristics.
32 outputs
±
24-VDC
20% (+19.2V to +28.8V),
100 mA max.,
transistor outputs, source mode outputs
3.4 I/O Modules (Optional)