Siemens G130 List Manual page 1543

Hide thumbs Also See for G130:
Table of Contents

Advertisement

F07330
Flying restart: Measured search current too low
Message value:
-
Message class:
Application/technological function faulted (17)
Drive object:
VECTOR_G
Component:
None
Reaction:
OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY
Cause:
During a flying restart, it was identified that the search current reached is too low.
It is possible that the motor is not connected.
Remedy:
Check the motor feeder cables.
F07331
Flying restart: Function not supported
Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Component:
None
Reaction:
OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY
Cause:
It is not possible to power up with the motor rotating (no flying restart).
In the following cases, the "flying restart" function is not supported:
Permanent-magnet synchronous motor (PMSM):
- operation with U/f characteristic.
- encoderless operation without a Voltage Sensing Module (VSM) being connected.
Separately excited synchronous motor (SESM):
- operation with U/f characteristic.
Remedy:
- deactivate the "flying restart" function (p1200 = 0).
- change the open-loop/closed-loop control mode (p1300).
- connect a Voltage Sensing Module (VSM) (voltage measurement).
N07332
Flying restart: maximum speed reduced
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Component:
None
Reaction:
NONE
Acknowledge:
NONE
Cause:
The maximum speed that can be reached is reduced; at very high speeds problems associated with the flying restart
can be encountered.
Possible causes:
- power ratio, power unit/motor too high
Remedy:
Parameter changes are not required.
Note:
A flying restart at speeds above 3000 rpm should be avoided.
A07350 (F)
Drive: Measuring probe parameterized to a digital output
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Component:
None
Reaction:
NONE
Acknowledge:
NONE
Cause:
The measuring probe is connected to a bi-directional digital input/output and the terminal is set as output.
Alarm value (r2124, interpret decimal):
8: DI/DO 8 (X122.9/X132.1)
9: DI/DO 9 (X122.10/X132.2)
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Propagation:
GLOBAL
Propagation:
GLOBAL
Propagation:
GLOBAL
Propagation:
LOCAL