Siemens G130 List Manual page 1565

Hide thumbs Also See for G130:
Table of Contents

Advertisement

A07486
EPOS: Intermediate stop missing
Message value:
-
Message class:
Application/technological function faulted (17)
Drive object:
VECTOR_G
Component:
None
Reaction:
NONE
Acknowledge:
NONE
Cause:
In the modes "traversing blocks" or "direct setpoint input/MDI" at the start of motion, the binector input "no
intermediate stop/intermediate stop" (BI: p2640) did not have a 1 signal.
Remedy:
Connect a 1 signal to the binector input "no intermediate stop/intermediate stop" (BI: p2640) and re-start motion.
A07487
EPOS: Reject traversing task missing
Message value:
-
Message class:
Application/technological function faulted (17)
Drive object:
VECTOR_G
Component:
None
Reaction:
NONE
Acknowledge:
NONE
Cause:
In the modes "traversing blocks" or "direct setpoint input/MDI" at the start of motion, the binector input "do not reject
traversing task/reject traversing task" (BI: p2641) does not have a 1 signal.
Remedy:
Connect a 1 signal to the binector input "do not reject traversing task/reject traversing task" (BI: p2641) and restart
motion.
F07488
EPOS: Relative positioning not possible
Message value:
-
Message class:
Application/technological function faulted (17)
Drive object:
VECTOR_G
Component:
None
Reaction:
OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
In the mode "direct setpoint input/MDI", for continuous transfer (p2649 = 1) relative positioning was selected (BI:
p2648 = 0 signal).
Remedy:
Check the control.
A07489
EPOS: Reference point correction outside the window
Message value:
-
Message class:
Application/technological function faulted (17)
Drive object:
VECTOR_G
Component:
None
Reaction:
NONE
Acknowledge:
NONE
Cause:
For the function "flying referencing" the difference between the measured position at the measuring probe and the
reference point coordinate lies outside the parameterized window.
Remedy:
- check the mechanical system.
- check the parameterization of the window (p2602).
F07490 (N)
EPOS: Enable signal withdrawn while traversing
Message value:
-
Message class:
Application/technological function faulted (17)
Drive object:
VECTOR_G
Component:
None
Reaction:
OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
- for a standard assignment, another fault may have occurred as a result of withdrawing the enable signals.
- the drive is in the "switching-on inhibited" state (for a standard assignment).
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Propagation:
GLOBAL
Propagation:
GLOBAL
Propagation:
GLOBAL
Propagation:
GLOBAL
Propagation:
GLOBAL
4 Faults and alarms
4.2 List of faults and alarms
1565

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents