Remedy:
The fault should be resolved as follows:
- select encoder commissioning (p0010 = 4).
- reset position tracking, position (p2720.2 = 1).
- deselect encoder commissioning (p0010 = 0).
The fault should then be acknowledged and the absolute encoder adjusted.
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F07449 (A)
Load gear: Position tracking actual position outside tolerance window
Message value:
%1
Message class:
Application/technological function faulted (17)
Drive object:
B_INF, ENC, VECTOR_G
Component:
None
Reaction:
Vector: OFF1 (NONE, OFF2, OFF3)
Infeed: NONE
Acknowledge:
IMMEDIATELY
Cause:
When switched off, the currently effective motor encoder was moved through a distance greater than was
parameterized in the tolerance window. It is possible that there is no longer any reference between the mechanical
system and encoder.
Note:
Only the motor encoder in the currently effective drive data set is monitored here. The actual effective drive data set
is displayed in x = r0051 and the corresponding motor encoder is specified in in p0187[x].
Fault value (r0949, interpret decimal):
Deviation (difference) to the last encoder position in increments of the absolute value after the measuring gear - if
one is being used. The sign designates the traversing direction.
Note:
The deviation (difference) found is also displayed in r2724.
See also: p2722 (Load gear position tracking tolerance window), r2724 (Load gear position difference)
Remedy:
Reset the position tracking as follows:
- select encoder commissioning (p0010 = 4).
- reset position tracking, position (p2720.2 = 1).
- deselect encoder commissioning (p0010 = 0).
The fault should then be acknowledged and, if necessary, the absolute encoder adjusted (p2507).
See also: p0010
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F07450 (A)
LR: Standstill monitoring has responded
Message value:
-
Message class:
Application/technological function faulted (17)
Drive object:
VECTOR_G
Component:
None
Reaction:
OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
After the standstill monitoring time (p2543) expired, the drive left the standstill window (p2542).
- position actual value inversion incorrectly set (p0410).
- standstill window set too small (p2542).
- standstill monitoring time set too low (p2543).
- position loop gain too low (p2538).
- position loop gain too high (instability/oscillation, p2538).
- mechanical overload.
- Connecting cable, motor/drive converter incorrect (phase missing, interchanged).
- when selecting motor identification, select tracking mode (BI: p2655[0] = 1 signal).
- when selecting function generator, select tracking mode (BI: p2655[0] = 1 signal) and deactivate position control
(BI:p2550 = 0 signal).
Remedy:
Check the causes and resolve.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Propagation:
GLOBAL
Propagation:
GLOBAL
4 Faults and alarms
4.2 List of faults and alarms
1555