Parameters
Parameter list
p0363[0...n]
Saturation characteristic flux 2 / Mot saturat.flux 2
VECTOR
Can be changed: C2, U, T
Data type: Floating Point
P-Group: Motor
Min
25.0 [%]
Description:
The saturation characteristics (flux as a function of the magnetizing current) is defined using 4 points.
This parameter specifies the y coordinate (flux) for the 2nd value pair of the characteristic.
Sets the second flux value of the saturation characteristic as a [%] referred to the rated motor voltage (p0304).
Dependency:
The following applies for the flux values:
p0362 < p0363 < p0364 < p0365
Refer to: p0367
Note:
p0363 = 100 % corresponds to the rated motor flux.
p0364[0...n]
Saturation characteristic flux 3 / Mot saturat.flux 3
VECTOR
Can be changed: C2, U, T
Data type: Floating Point
P-Group: Motor
Min
25.0 [%]
Description:
The saturation characteristics (flux as a function of the magnetizing current) is defined using 4 points.
This parameter specifies the y coordinate (flux) for the 3rd value pair of the characteristic.
Sets the third flux value of the saturation characteristic as a [%] referred to the rated motor voltage (p0304).
Dependency:
The following applies for the flux values:
p0362 < p0363 < p0364 < p0365
Refer to: p0368
Note:
p0364 = 100 % corresponds to the rated motor flux.
p0365[0...n]
Saturation characteristic flux 4 / Mot saturat.flux 4
VECTOR
Can be changed: C2, U, T
Data type: Floating Point
P-Group: Motor
Min
25.0 [%]
Description:
The saturation characteristics (flux as a function of the magnetizing current) is defined using 4 points.
This parameter specifies the y coordinate (flux) for the 4th value pair of the characteristic.
Sets the fourth flux value of the saturation characteristic as a [%] referred to the rated motor voltage (p0304).
Dependency:
The following applies for the flux values:
p0362 < p0363 < p0364 < p0365
Refer to: p0369
Note:
p0365 = 100 % corresponds to the rated motor flux.
1-78
Data set: MDS
Units group: PERCENT
Max
300.0 [%]
Data set: MDS
Units group: PERCENT
Max
300.0 [%]
Data set: MDS
Units group: PERCENT
Max
300.0 [%]
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Access level: 4
Function diagram: -
Unit selection: -
Factory setting
85.0 [%]
Access level: 4
Function diagram: -
Unit selection: -
Factory setting
115.0 [%]
Access level: 4
Function diagram: -
Unit selection: -
Factory setting
125.0 [%]