F01513 (A)
BICO: Spanning DO between different normalizations
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The requested interconnection was set up. However, a conversion is made between the BICO output and BICO input
using the reference values.
An interconnection is made between different drive objects and the BICO output has different normalized units than
the BICO input or the normalized units are the same but the reference values are different.
Example:
The BICO output has, as standard unit, voltage and the BICO input has current; both lie in different drive objects.
This means that the factor p2002 (contains the reference value for current) / p2001 (contains the reference value for
voltage) is calculated between the BICO output and BICO input.
Fault value (r0949, decimal):
Parameter number of the BICO input (signal receiver).
Remedy:
No correction needed.
Reaction upon A:
NONE
Acknowledge
NONE
upon A:
A01514 (F)
BICO: Error when writing during a reconnect
Reaction:
NONE
Acknowledge:
NONE
Cause:
During a reconnect operation (e.g. at run-up or download - but cannot occur in normal operation) a parameter was
not able to be written into.
Example:
When writing to a double word BICO input in the second index, the memory areas overlap (e.g. p8861). The param-
eter is then reset to the factor setting.
Alarm value (r2124, decimal):
Parameter number of the BICO input (signal receiver).
Remedy:
Reaction upon F:
NONE
Acknowledge
IMMEDIATELY
upon F:
F01590 (A)
Drive: Service/maintenance interval expired
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The selected service/maintenance interval (p0651) for this drive was reached.
Fault value (r0949, decimal):
Motor data set number.
See also: p0650, p0651
Remedy:
Carry-out service/maintenance and reset the service/maintenance interval (p0651).
Reaction upon A:
NONE
Acknowledge
NONE
upon A:
F01600
SI CU: STOP A initiated
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (power on)
Cause:
The Safety Integrated function on the control unit has detected a fault and initiated a STOP A (pulse cancellation via
the safety shutdown path of the control unit).
- forced checking procedure of the safety shutdown path of the control unit unsuccessful.
- subsequent response to fault F01611 (defect in a monitoring channel).
Fault value (r0949, decimal):
0: Stop request from the motor module.
1005: Pulses cancelled although SH not selected and there is not internal STOP A present.
1010: Pulses enabled although SH is selected or an internal STOP A is present.
1015: Feedback of the safe pulse cancellation for motor modules connected in parallel are different.
9999: Subsequent response to fault F01611.
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Faults and Alarms
List of faults and alarms
3-537