Parameters
Parameter list
p2119[0...19]
Setting the message type / Message type
All objects
Can be changed: U, T
Data type: Integer16
P-Group: Messages
Min
1
Description:
Sets the message type for the selected fault or alarm.
Values:
1:
2:
3:
Dependency:
Selects the fault or alarm selection and sets the required type of message realized under the same index.
Refer to: p2118
Notice:
It is not possible to re-parameterize the message type for the existing faults or alarms.
Note:
The message type can only be changed for messages with the appropriate identification.
Example:
F12345(A) --> Fault F12345 can be changed to alarm A12345.
In this case, the message number that may be possibly entered in p2100[0...19] and p2126[0...19] is automatically
removed.
r2120
Sum of fault and alarm buffer changes / Sum buffer changed
All objects
Can be changed: -
Data type: Unsigned16
P-Group: Messages
Min
-
Description:
Displays the sum of all of the fault and alarm buffer changes in the drive unit.
Dependency:
Refer to: r0944, r2121
r2121
Counter, alarm buffer changes / Alrm buff changed
All objects
Can be changed: -
Data type: Unsigned16
P-Group: Messages
Min
-
Description:
This counter is incremented every time the alarm buffer changes.
Dependency:
Refer to: r2110, r2122, r2123, r2124, r2125
r2122[0...7]
Alarm code / Alarm code
All objects
Can be changed: -
Data type: Unsigned16
P-Group: Messages
Min
-
Description:
Displays the number of alarms that have occurred.
Dependency:
Refer to: r2110, r2123, r2124, r2125, r2134, r2145, r2146
Note:
Alarm buffer structure (general principle):
r2122[0], r2124[0], r2123[0], r2125[0] --> alarm 1 (the oldest)
...
r2122[7], r2124[7], r2123[7], r2125[7] --> Alarm 8 (the latest)
1-256
Fault (F)
Alarm (A)
No message (N)
Data set: -
Units group: -
Max
3
Data set: -
Units group: -
Max
-
Data set: -
Units group: -
Max
-
Data set: -
Units group: -
Max
-
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Access level: 3
Function diagram: 1750,
8075
Unit selection: -
Factory setting
1
Access level: 4
Function diagram: 8065
Unit selection: -
Factory setting
-
Access level: 3
Function diagram: 8065
Unit selection: -
Factory setting
-
Access level: 2
Function diagram: 1750,
8065
Unit selection: -
Factory setting
-