Parameters
Parameter list
r1315
Voltage boost total / U_boost total
VECTOR
Can be changed: -
Data type: Floating Point
P-Group: V/f control
Min
- [Veff]
Description:
Displays the total resulting voltage boost in volt (p1310 + p1311).
p1320[0...n]
V/f control programmable characteristic frequency 1 / Uf char f1
VECTOR
Can be changed: U, T
Data type: Floating Point
P-Group: V/f control
Min
0.00 [Hz]
Description:
The programmable characteristic for the V/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the first point along the characteristic.
Dependency:
Selects the freely programmable characteristic using p1300 = 3.
Refer to: p1300, p1310, p1311, p1321, p1322, p1323, p1324, p1325, p1326, p1327
Note:
Linear interpolation is carried-out between the points 0 Hz / p1310, p1320 / p1321 ... p1326 / p1327.
The voltage boost when accelerating (p1311) is also applied to the freely programmable V/Hz characteristic.
p1321[0...n]
V/f control programmable characteristic voltage 1 / Uf char U1
VECTOR
Can be changed: U, T
Data type: Floating Point
P-Group: V/f control
Min
0.0 [Veff]
Description:
The programmable characteristic for the V/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the first point along the characteristic.
Dependency:
Selects the freely programmable characteristic using p1300 = 3.
Refer to: p1310, p1311, p1320, p1322, p1323, p1324, p1325, p1326, p1327
Note:
Linear interpolation is carried-out between the points 0 Hz / p1310, p1320 / p1321 ... p1326 / p1327.
The voltage boost when accelerating (p1311) is also applied to the freely programmable V/Hz characteristic.
p1322[0...n]
V/f control programmable characteristic frequency 2 / Uf char f2
VECTOR
Can be changed: U, T
Data type: Floating Point
P-Group: V/f control
Min
0.00 [Hz]
Description:
The programmable characteristic for the V/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the second point along the characteristic.
Dependency:
Refer to: p1310, p1311, p1320, p1321, p1323, p1324, p1325, p1326, p1327
1-174
Data set: -
Units group: VOLTAGE_AC_EFF Unit selection: -
Max
- [Veff]
Data set: DDS
Units group: FREQUENCY
Max
3000.00 [Hz]
Data set: DDS
Units group: VOLTAGE_AC_EFF Unit selection: -
Max
10000.0 [Veff]
Data set: DDS
Units group: FREQUENCY
Max
3000.00 [Hz]
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Access level: 4
Function diagram: 6300
Factory setting
- [Veff]
Access level: 3
Function diagram: 6300
Unit selection: -
Factory setting
0.00 [Hz]
Access level: 3
Function diagram: 6300
Factory setting
0.0 [Veff]
Access level: 3
Function diagram: 6300
Unit selection: -
Factory setting
0.00 [Hz]