r0999[0...99]
List of modified parameters 10 / List changd par10
All objects
Can be changed: -
Data type: Unsigned16
P-Group: -
Min
-
Description:
Displays those parameters with a value other than the factory setting for this drive.
Dependency:
Refer to: r0990, r0991
Note:
Modified parameters are displayed in indices 0 to 98. If an index contains the value 0, then the list ends here.
This list completely comprises the following parameters:
r0990[0...99], r0991[0...99] ... r0999[0...99]
The parameters in this list are not displayed in the expert list of the commissioning software. However, they can be
read from a higher-level control system (e.g. PROFIBUS master).
p1000[0...n]
Macro connector inputs (CI) for speed setpoints / Macro CI n_set
VECTOR
Can be changed: C2, T
Data type: Unsigned32
P-Group: Commands
Min
0
Description:
Runs the appropriate ACX file on the CompactFlash Card.
The connector inputs (CI) for the speed setpoints of the appropriate command data set (CDS) are appropriately
interconnected.
The selected ACX file must be located in the following directory:
... /PMACRO/<drive object>/P1000/PMxxxxxx.ACX
Example:
p1000 = 6 --> the file PM000006.ACX is run.
Dependency:
The ACX file to be run must be created according to the definition for ACX macros and must be saved in the direc-
tory intended on the CompactFlash Card.
Refer to: p0015, p0700, p1500
Note:
CI: Connector input
p1001[0...n]
CO: Fixed speed setpoint 1 / n_set_fixed 1
VECTOR
Can be changed: U, T
Data type: Floating Point
P-Group: Setpoints
Min
-210000.000 [1/min]
Description:
Sets a value for the fixed speed / velocity setpoint 1.
Dependency:
Refer to: p1020, p1021, p1022, p1023, r1024, r1197
p1002[0...n]
CO: Fixed speed setpoint 2 / n_set_fixed 2
VECTOR
Can be changed: U, T
Data type: Floating Point
P-Group: Setpoints
Min
-210000.000 [1/min]
Description:
Sets a value for the fixed speed / velocity setpoint 2.
Dependency:
Refer to: p1020, p1021, p1022, p1023, r1024, r1197
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Data set: -
Units group: -
Max
-
Data set: CDS
Units group: -
Max
999999
Data set: DDS
Units group: SPEED_ROT
Max
210000.000 [1/min]
Data set: DDS
Units group: SPEED_ROT
Max
210000.000 [1/min]
Parameters
Parameter list
Access level: 4
Function diagram: -
Unit selection: -
Factory setting
-
Access level: 1
Function diagram: -
Unit selection: -
Factory setting
0
Access level: 2
Function diagram: 3010
Unit selection: -
Factory setting
0.000 [1/min]
Access level: 2
Function diagram: 3010
Unit selection: -
Factory setting
0.000 [1/min]
1-135