p0650[0...n]
Actual motor operating time / t_motor actual
VECTOR
Can be changed: T
Data type: Unsigned32
P-Group: Motor
Min
0
Description:
Displays the motor operating time for the appropriate drive.
The motor operating time counter is started when the pulses are enabled. When the pulse enable is withdrawn, the
counter is held and the value saved. The persistence is in the NVRAM - this means that if the module is equipped
with an NVRAM, the value is saved in a non-volatile fashion; otherwise not.
If p0651 is at 0, the counter is de-activated.
Display in hours.
Dependency:
Refer to: p0651
Refer to: F01590
Note:
The value in p0650 can only be reset to 0.
p0651[0...n]
Motor operating time service interval / t_motor service
VECTOR
Can be changed: T
Data type: Unsigned32
P-Group: Motor
Min
0
Description:
Sets the service/maintenance intervals for the appropriate drive.
If the selected motor operating time is reached (p0650), then the appropriate fault is output.
Display in hours.
Dependency:
Refer to: p0650
Refer to: F01590
Note:
For p0651 = 0 [h], the motor operating time counter is disabled.
p0700[0...n]
Macro binector input (BI) / Macro BI
VECTOR
Can be changed: C2, T
Data type: Unsigned32
P-Group: Commands
Min
0
Description:
Runs the appropriate ACX file on the CompactFlash Card.
The binector inputs (BI) of the appropriate command data set (CDS) are appropriately interconnected.
The selected ACX file must be located in the following directory:
... /PMACRO/<drive object>/P700/PMxxxxxx.ACX
Example:
p0700 = 6 --> the file PM000006.ACX is run.
Dependency:
The ACX file to be run must be created according to the definition for ACX macros and must be saved in the direc-
tory intended on the CompactFlash Card.
Refer to: p0015, p1000, p1500
Note:
BI: Binector input
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Data set: MDS
Units group: -
Max
4294967295
Data set: MDS
Units group: -
Max
99999
Data set: CDS
Units group: -
Max
999999
Parameters
Parameter list
Access level: 3
Function diagram: -
Unit selection: -
Factory setting
0
Access level: 3
Function diagram: -
Unit selection: -
Factory setting
0
Access level: 1
Function diagram: -
Unit selection: -
Factory setting
0
1-105