Faults and Alarms
List of faults and alarms
F32886
CU DRIVE-CLiQ: Error when sending DRIVE-CLiQ data
Reaction:
NONE (OFF1, OFF2)
Acknowledge:
IMMEDIATELY
Cause:
DRIVE-CLiQ communications error between the control unit and the encoder involved. Data were not able to be sent.
Fault value (r0949, hexadecimal):
41: Telegram type does not match send list.
Remedy:
- carry-out a POWER ON.
F32887
CU DRIVE-CLiQ: Component faulted
Reaction:
NONE (OFF1, OFF2)
Acknowledge:
IMMEDIATELY
Cause:
Fault detected on the DRIVE-CLiQ component involved. Faulty hardware cannot be excluded.
Fault value (r0949, hexadecimal):
20: Error in the telegram header.
23: Receive error: The telegram buffer memory contains an error.
42: Send error: The telegram buffer memory contains an error.
43: Send error: The telegram buffer memory contains an error.
60: Response received too late during runtime measurement.
61: Time taken to exchange characteristic data too long.
Remedy:
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
- check the electrical cabinet design and cable routing for EMC compliance
- if required, use another DRIVE-CLiQ socket (p9904).
- replace the component involved.
F32895
CU DRIVE-CLiQ: Cyclic data transfer error
Reaction:
NONE (OFF1, OFF2)
Acknowledge:
IMMEDIATELY
Cause:
DRIVE-CLiQ communications error between the control unit and the encoder involved.
Fault value (r0949, hexadecimal):
0B: Synchronization error during alternating cyclic data transfer.
Remedy:
- carry-out a POWER ON.
See also: p9915
F32897
DRIVE-CLiQ: No communications to the components
Reaction:
ENCODER (DCBRAKE, NONE, OFF1, OFF2, OFF3, STOP1, STOP2)
Acknowledge:
power on (IMMEDIATELY)
Cause:
Communications with the DRIVE-CLiQ component specified by the fault value is not possible.
One cause can be, e.g. that a DRIVE-CLiQ cable has been withdrawn.
Fault value (r0949, decimal):
Component ID.
Remedy:
- check the DRIVE-CLiQ connections.
- carry-out a POWER ON.
F32899 (N, A)
Encoder 2: Unknown fault
Reaction:
NONE (DCBRAKE, OFF1, OFF2, OFF3, STOP1, STOP2)
Acknowledge:
IMMEDIATELY (power on)
Cause:
A fault occurred on the sensor module for encoder 2 that cannot be interpreted by the control unit firmware.
This can occur if the firmware on the sensor module for encoder 2 is more recent than the firmware on the control
unit.
Fault value (r0949, decimal):
Fault number.
If required, the significance of this new fault can be referred to in a more recent description of the control unit.
Remedy:
- replace the firmware on the sensor module by an older firmware version (r0148).
- upgrade the firmware on the control unit (r0018).
Reaction upon N:
NONE
Acknowledge
NONE
upon N:
3-624