Note:
For p0300 = 10000, the motor parameters are automatically downloaded if the motor has integrated encoder evalu-
ation. The input is ineffective if there is no integrated encoder sensing.
If a motor type has not been selected (p0300 = 0), then the drive commissioning routine cannot be exited.
A motor type with a value above p0300 >= 100 describes motors for which a motor parameter list exists.
Motor types with a value below p0300 < 100 correspond to the selection of an unlisted motor. When appropriately
selected, this means that the motor parameters are pre-assigned the settings for an unlisted motor.
If a catalog motor is selected (p0300 >= 100) and an associated motor code number (p0301), then the parameters,
that are associated if this list, cannot be changed (write protection). The write protection is canceled if the motor
type p0300 is set to a non-Siemens motor that matches p0301 (e.g. p0300 = 2 for p0301 = 2xxxx).
This also applies to the parameters of the integrated encoder sensing. In this case p0300 can only be set to p0300
= 10000 (read motor parameters) or to the corresponding non-Siemens motor (first digit of the motor code number)
in order to be able to cancel the write protection.
p0301[0...n]
Motor code number selection / Mot code No. sel
VECTOR
Can be changed: C2, U
Data type: Unsigned16
P-Group: Motor
Min
0
Description:
The parameter is used to select a motor from a motor parameter list.
When changing the code number (with the exception to the value 0), all of the motor parameters are pre-assigned
from the internally available parameter lists.
Dependency:
Only code numbers for motor types can be selected that correspond to the motor type selected in p0300.
Refer to: p0300
Note:
The motor code number can only be changed if the matching list motor was first selected in p0300.
If the motor has its own integrated encoder evaluation, then p0301 cannot be changed. In this case, p0301 is auto-
matically written to the code number of the motor parameter read-in (r0302) if p0300 is set to 10000.
When selecting a list motor (p0300 >= 100), drive commissioning can only be exited if a code number is selected.
r0302[0...n]
Motor code number of integrated encoder evaluation / Motor code int enc
VECTOR
Can be changed: -
Data type: Unsigned16
P-Group: Motor
Min
-
Description:
Displays the motor code number of the motor data stored in the integrated encoder evaluation.
Note:
Drive commissioning can only be exited if the code number that was downloaded (r0302) matches the stored code
number (p0301). If the numbers differ, then the motor data set should be re-loaded using p0300 = 10000.
The motor data are always expected from the first encoder that is assigned to the drive data sets (refer to p0187 =
encoder 1) data set number.
p0304[0...n]
Rated motor voltage / Mot U_rated
VECTOR
Can be changed: C2
Data type: Floating Point
P-Group: Motor
Min
0 [Veff]
Description:
Sets the rated motor voltage (rating plate).
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Data set: MDS
Units group: -
Max
65535
Data set: MDS
Units group: -
Max
-
Data set: MDS
Units group: VOLTAGE_AC_EFF Unit selection: -
Max
20000 [Veff]
Parameters
Parameter list
Access level: 2
Function diagram: -
Unit selection: -
Factory setting
0
Access level: 2
Function diagram: -
Unit selection: -
Factory setting
-
Access level: 1
Function diagram: 6300,
6724
Factory setting
0 [Veff]
1-65

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents