When the maximum speed is changed, the pulse frequency P1800 is automatically limited to this minimum ratio. It
is not permissible to reduce the pulse frequency if this would result in this ratio being fallen below.
p1825
Converter valve threshold voltage / Threshold voltage
VECTOR
Can be changed: U, T
Data type: Floating Point
P-Group: Modulation
Min
0.0 [Veff]
Description:
Sets the threshold voltage drop of the valves (power semiconductor devices) to be compensated.
Note:
The value is automatically calculated in the motor data identification routine.
p1828
Compensation valve lockout time phase U / Comp t_interl ph U
VECTOR
Can be changed: U, T
Data type: Floating Point
P-Group: Modulation
Min
0.00 [µs]
Description:
Sets the valve lockout time to compensate for phase U.
Note:
The value is automatically calculated in the motor data identification routine.
p1829
Compensation valve lockout time phase V / Comp t_interl ph V
VECTOR
Can be changed: U, T
Data type: Floating Point
P-Group: Modulation
Min
0.00 [µs]
Description:
Sets the valve lockout time to compensate for phase V.
p1830
Compensation valve lockout time phase W / Comp t_interl ph W
VECTOR
Can be changed: U, T
Data type: Floating Point
P-Group: Modulation
Min
0.00 [µs]
Description:
Sets the valve lockout time to compensate for phase W.
p1832
Deadtime compensation current level / t_dead_comp I_lev
VECTOR
Can be changed: U, T
Data type: Floating Point
P-Group: Modulation
Min
0.0 [Aeff]
Description:
Above the current level, the deadtime - resulting from the converter switching delays - is compensated by a previ-
ously calculated, constant value . If the relevant phase current setpoint falls below the absolute value defined by
p1832, the correction value for this phase is continuously reduced.
Dependency:
The factor setting of p1832 is automatically set to 0.02 * rated drive converter current (r0207).
If the actual operating frequency exceeds the value of p1831, then p1832 is not applied!
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Data set: -
Units group: VOLTAGE_AC_EFF Unit selection: -
Max
100.0 [Veff]
Data set: -
Units group: TIME_M6
Max
1000000.00 [µs]
Data set: -
Units group: TIME_M6
Max
1000000.00 [µs]
Data set: -
Units group: TIME_M6
Max
1000000.00 [µs]
Data set: -
Units group: CURRENT_AC_EFF Unit selection: -
Max
10000.0 [Aeff]
Parameters
Parameter list
Access level: 4
Function diagram: -
Factory setting
1.0 [Veff]
Access level: 4
Function diagram: -
Unit selection: -
Factory setting
0.00 [µs]
Access level: 4
Function diagram: -
Unit selection: -
Factory setting
0.00 [µs]
Access level: 4
Function diagram: -
Unit selection: -
Factory setting
0.00 [µs]
Access level: 3
Function diagram: -
Factory setting
0.0 [Aeff]
1-219