p2200[0...n]
BI: Technology controller enable / Tec_ctr enable
VECTOR (Tech ctrl) Can be changed: U, T
Data type: Unsigned32
P-Group: Technology
Min
-
Description:
Sets the signal source to switch-in/switch-out the technology controller.
The technology controller is switched-in with a 1 signal.
p2201[0...n]
CO: Technology controller, fixed value 1 / Tec_ctr fix val 1
VECTOR (Tech ctrl) Can be changed: U, T
Data type: Floating Point
P-Group: Technology
Min
-200.00 [%]
Description:
Sets the value for fixed value 1 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
p2202[0...n]
CO: Technology controller, fixed value 2 / Tec_ctr fix val 2
VECTOR (Tech ctrl) Can be changed: U, T
Data type: Floating Point
P-Group: Technology
Min
-200.00 [%]
Description:
Sets the value for fixed value 2 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
p2203[0...n]
CO: Technology controller, fixed value 3 / Tec_ctr fix val 3
VECTOR (Tech ctrl) Can be changed: U, T
Data type: Floating Point
P-Group: Technology
Min
-200.00 [%]
Description:
Sets the value for fixed value 3 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
p2204[0...n]
CO: Technology controller, fixed value 4 / Tec_ctr fix val 4
VECTOR (Tech ctrl) Can be changed: U, T
Data type: Floating Point
P-Group: Technology
Min
-200.00 [%]
Description:
Sets the value for fixed value 4 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Data set: CDS
Units group: -
Max
-
Data set: DDS
Units group: PERCENT
Max
200.00 [%]
Data set: DDS
Units group: PERCENT
Max
200.00 [%]
Data set: DDS
Units group: PERCENT
Max
200.00 [%]
Data set: DDS
Units group: PERCENT
Max
200.00 [%]
Parameters
Parameter list
Access level: 2
Function diagram: 7958
Unit selection: -
Factory setting
0
Access level: 2
Function diagram: 7950
Unit selection: -
Factory setting
0.00 [%]
Access level: 2
Function diagram: 7950
Unit selection: -
Factory setting
10.00 [%]
Access level: 2
Function diagram: 7950
Unit selection: -
Factory setting
20.00 [%]
Access level: 2
Function diagram: 7950
Unit selection: -
Factory setting
30.00 [%]