Faults and Alarms
List of faults and alarms
Cause:
An error was detected when evaluating the temperature sensor set in p0600 and p0601.
Possible causes:
- wire breakage or sensor not connected (KTY: R > 1630 Ohm).
- measured resistance too low (PTC: R < 30 Ohm, KTY: R < 340 Ohm).
Note:
For induction motors, the model value is selected for the temperature monitoring.
For synchronous motors, the temperature monitoring is disabled and the ambient temperature is displayed in r0035.
If alarm A07015 is present, the time in p0607 is started. If the fault is still present after this time has expired, then
fault F07016 is output; however, at the earliest, 1 s after alarm A07015.
See also: p0607
Remedy:
- check that the sensor is connected correctly.
- check the parameterization (p0600, p0601).
- induction motors: Deactivate temperature sensor fault (p0607 = 0).
See also: p0600, p0601, p0607
N07044
Drive: Rotor position identification completed
Reaction:
OFF2
Acknowledge:
NONE
Cause:
The message is used to signal the sequential control that the rotor position identification routine has been completed.
Remedy:
The message is used to signal the sequential control that the rotor position identification routine has been completed.
F07080
Drive: Open-loop/closed-loop control parameterization error
Reaction:
NONE
Acknowledge:
IMMEDIATELY (power on)
Cause:
Closed-loop control parameters have been parameterized incorrectly (e.g. p0350 = R_stator = 0).
Fault value (r0949, decimal):
The fault value includes the parameter number involved.
See also: p0300, p0311, p0341, p0344, p0350, p0354, p0356, p0358, p0360, p0400, p0640, p1082, p1300
Remedy:
Modify the parameter indicated in the fault value (r0949) (e.g. p0640 = current limit > 0).
See also: p0311, p0341, p0344, p0350, p0354, p0356, p0358, p0360, p0400, p0640, p1082
F07082
Macro: Execution not possible
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The macro cannot be executed for the following reasons:
Fault for the trigger parameter itself:
- trigger parameter (e.g. p0015) does not match that in the specified file.
- data type of the TAG index, number of bit is not U16 or the data type of the TAG Dotype is not I16.
Faults for the parameters to be set:
- commissioning was carried-out (p0009 = 0) and a wait condition, required after commissioning, was not defined in
the ACX file.
- parameter cannot be written into because it is either read-only or does not exist.
- parameter cannot be written into as the data is either incomplete or corrupt/incorrect (e.g. incorrect data type,
value range or assignment incorrect).
- factory setting is not possible for this drive object (e.g. the drive object does not exist).
Fault value (r0949, decimal):
The parameter number involved, if this is available.
Remedy:
- check the parameter involved.
- check the macro file and connections.
See also: p0015, p0700, p1000, p1500
F07083
Macro: ACX file not found
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The ACX file (PM file) to be executed was not able to be found in the appropriate directory.
Fault value (r0949, decimal):
Parameter number with which the execution was started.
See also: p0015
3-558
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004