Siemens SINAMICS G List Manual page 671

Table of Contents

Advertisement

Cause:
An alarm has occurred for the drive object with this object number.
Alarm value (r2124, decimal):
First alarm that has occurred for this drive object.
Remedy:
Evaluate the alarm buffer of the specified object.
A40162
Alarm on drive object with object number 62
Reaction:
NONE
Acknowledge:
NONE
Cause:
An alarm has occurred for the drive object with this object number.
Alarm value (r2124, decimal):
First alarm that has occurred for this drive object.
Remedy:
Evaluate the alarm buffer of the specified object.
F40801
CX32 DRIVE-CLiQ: Sign-of-life missing
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communications error has occurred between the control unit and the controller extension involved.
The nodes do not send and receive in synchronism.
Fault value (r0949, hexadecimal):
0A: The sign-of-life bit in the receive telegram is not set.
Remedy:
- carry-out a POWER ON.
- replace the component involved.
See also: p9916
F40820
CX32 DRIVE-CLiQ: Telegram error
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communications error has occurred between the control unit and the controller extension involved.
Fault value (r0949, hexadecimal):
01: CRC error.
02: Telegram is shorter than specified in the length byte or in the receive list.
03: Telegram is longer than specified in the length byte or in the receive list.
04: The length of the receive telegram does not match the receive list.
05: The type of the receive telegram does not match the receive list.
06: The address of the controller extension in the telegram and in the receive list do not match.
07: Controller extension expects a SYNC telegram, but the receive telegram is not a SYNC telegram.
08: Controller extension does not expect a SYNC telegram, but the receive telegram is a SYNC telegram.
09: The error bit in the receive telegram is set.
10: The receive telegram is too early.
Remedy:
- carry-out a POWER ON.
- check the electrical cabinet design and cable routing for EMC compliance
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
See also: p9916
F40835
CX32 DRIVE-CLiQ: Cyclic data transfer error
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communications error has occurred between the control unit and the controller extension involved.
The nodes do not send and receive in synchronism.
Fault value (r0949, hexadecimal):
21: The cyclic telegram has not been received.
22: Timeout in the telegram receive list.
40: Timeout in the telegram send list.
Remedy:
- carry-out a POWER ON.
- replace the component involved.
See also: p9916
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Faults and Alarms
List of faults and alarms
3-671

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents