Siemens SINAMICS G List Manual page 321

Table of Contents

Advertisement

r7200[0...n]
Parallel circuit configuration, power module overload I2T / PM overload I2T
VECTOR (Parallel)
Can be changed: -
Data type: Floating Point
P-Group: Displays, signals
Min
- [%]
Description:
Displays the overload of the particular power module in a parallel circuit configuration calculated using the I2t func-
tion. The maximum value of all power modules is displayed in r0036.
r7201[0...n]
Parallel circuit configuration, power module, maximum inverter temperatures / PM
temp max inv
VECTOR (Parallel)
Can be changed: -
Data type: Floating Point
P-Group: Displays, signals
Min
- [°C]
Description:
Displays the maximum inverter temperature in the power module for a parallel circuit configuration.
The maximum value of all power modules is displayed in r0037[0].
r7202[0...n]
Parallel circuit configuration, power module, maximum depletion layer temperatures
/ PM TempMaxDepLayer
VECTOR (Parallel)
Can be changed: -
Data type: Floating Point
P-Group: Displays, signals
Min
- [°C]
Description:
Displays the maximum barrier junction temperature in the power module for a parallel circuit configuration.
The maximum value of all power modules is displayed in r0037[1].
r7203[0...n]
Parallel circuit configuration, power module, maximum rectifier temperatures / PM
temp max rect
VECTOR (Parallel)
Can be changed: -
Data type: Floating Point
P-Group: Displays, signals
Min
- [°C]
Description:
Displays the maximum rectifier temperature in the power module for a parallel circuit configuration.
The maximum value of all power modules is displayed in r0037[2].
r7204[0...n]
Parallel circuit configuration, power module air intake temperatures / PM temp air
intake
VECTOR (Parallel)
Can be changed: -
Data type: Floating Point
P-Group: Displays, signals
Min
- [°C]
Description:
Displays the air intake temperature in the power module for a parallel circuit configuration.
The maximum value of all power modules is displayed in r0037[3].
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Data set: PDS
Units group: PERCENT
Max
- [%]
Data set: PDS
Units group: TEMPERATURE
Max
- [°C]
Data set: PDS
Units group: TEMPERATURE
Max
- [°C]
Data set: PDS
Units group: TEMPERATURE
Max
- [°C]
Data set: PDS
Units group: TEMPERATURE
Max
- [°C]
Parameters
Parameter list
Access level: 3
Function diagram: -
Unit selection: -
Factory setting
- [%]
Access level: 3
Function diagram: -
Unit selection: -
Factory setting
- [°C]
Access level: 3
Function diagram: -
Unit selection: -
Factory setting
- [°C]
Access level: 3
Function diagram: -
Unit selection: -
Factory setting
- [°C]
Access level: 3
Function diagram: -
Unit selection: -
Factory setting
- [°C]