p1740[0...n]
Gain resonance damping for sensorless closed loop control / Gain res_damp
VECTOR (n/M)
Can be changed: U, T
Data type: Floating Point
P-Group: Control
Min
0.000
Description:
Defines the gain of the controller for resonance damping for operation with sensorless vector control in the range
that current is impressed.
p1744[0...n]
Motor model speed threshold stall detection / MotMod n_thr stall
VECTOR (n/M)
Can be changed: U, T
Data type: Floating Point
P-Group: Control
Min
0.00 [1/min]
Description:
Sets the speed threshold value to detect a stalled motor.
If the adaptation controller output exceeds the parameterized speed difference, then bit 11 in status word p1408 is
set.
Dependency:
If a stalled drive is detected (p1408.11 set), fault 7902 is output after the delay time in p2178.
Refer to: p2178
Note:
Speed monitoring is only effective in operation with a speed encoder (refer to p1300).
p1745[0...n]
Motor model error threshold stall detection / MotMod ThreshStall
VECTOR (n/M)
Can be changed: U, T
Data type: Floating Point
P-Group: Control
Min
0.0 [%]
Description:
Sets the fault threshold in order to detect a motor that has stalled.
If the error signal (r1746) exceeds the parameterized error threshold, then bit 12 in status word p1408 is set.
Dependency:
If a stalled drive is detected (p1408.12 set), fault 7902 is output after the delay time set in P2178.
Refer to: p2178
Note:
Monitoring is only effective in the low-speed range (below p1755 * p1756).
r1746
Motor model error signal stall detection / MotMod sig stall
VECTOR (n/M)
Can be changed: -
Data type: Floating Point
P-Group: Control
Min
- [%]
Description:
Signal to initiate stall detection
Note:
The signal is not calculated while magnetizing and only in the low speed range (below p1755 * p1756).
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Data set: DDS
Units group: -
Max
10.000
Data set: DDS
Units group: SPEED_ROT
Max
210000.00 [1/min]
Data set: DDS
Units group: PERCENT
Max
1000.0 [%]
Data set: -
Units group: PERCENT
Max
- [%]
Parameters
Parameter list
Access level: 3
Function diagram: -
Unit selection: -
Factory setting
0.025
Access level: 3
Function diagram: -
Unit selection: -
Factory setting
100.00 [1/min]
Access level: 3
Function diagram: -
Unit selection: -
Factory setting
5.0 [%]
Access level: 4
Function diagram: -
Unit selection: -
Factory setting
- [%]
1-209