Parameters
Parameter list
p0350[0...n]
Motor stator resistance, cold / Mot R_stator cold
VECTOR
Can be changed: C2, U, T
Data type: Floating Point
P-Group: Motor
Min
0.00000 [Ohm]
Description:
Sets the stator resistance of the motor at ambient temperature p0625.
Dependency:
Refer to: p0625
Note:
The parameter is automatically preset for motors from the motor list (p0301).
The motor identification routine determines the stator resistance from the total stator resistance minus the cable
resistance (p0352).
p0352[0...n]
Cable resistance (component of the stator resistance) / Mot R_cable cold
VECTOR
Can be changed: C2, U, T
Data type: Floating Point
P-Group: Motor
Min
0.00000 [Ohm]
Description:
Resistance of the power cable between the motor module and motor.
Note:
The parameter influences the temperature adaptation of the stator resistance.
The motor identification routine does not change the cable resistance. This is subtracted from the total measured
stator resistance in order to calculate the stator resistance (p0350, p0352).
p0354[0...n]
Motor rotor resistance, cold / Mot R_rotor cold
VECTOR
Can be changed: C2, U, T
Data type: Floating Point
P-Group: Motor
Min
0.00000 [Ohm]
Description:
Sets the the rotor/secondary section resistance of the motor at the ambient temperature p0625.
This parameter value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor identifica-
tion routine (p1910).
Dependency:
Refer to: p0625
Note:
The parameter is not used for synchronous motors (p0300 = 2xx).
The parameter is automatically preset for motors from the motor list (p0301).
p0356[0...n]
Motor stator leakage inductance / Mot L_stator leak.
VECTOR
Can be changed: C2, U, T
Data type: Floating Point
P-Group: Motor
Min
0.00000 [mH]
Description:
Induction motor: Sets the rotor leakage inductance of the motor.
Synchronous motor: Sets the stator quadrature axis inductance of the motor.
This parameter value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor identifica-
tion routine (p1910).
Note:
The parameter is automatically preset for motors from the motor list (p0301).
1-76
Data set: MDS
Units group: RESISTANCE
Max
2000.00000 [Ohm]
Data set: MDS
Units group: RESISTANCE
Max
120.00000 [Ohm]
Data set: MDS
Units group: RESISTANCE
Max
300.00000 [Ohm]
Data set: MDS
Units group: INDUCTANCE_M3
Max
1000.00000 [mH]
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Access level: 2
Function diagram: -
Unit selection: -
Factory setting
0.00000 [Ohm]
Access level: 3
Function diagram: -
Unit selection: -
Factory setting
0.00000 [Ohm]
Access level: 3
Function diagram: -
Unit selection: -
Factory setting
0.00000 [Ohm]
Access level: 3
Function diagram: -
Unit selection: -
Factory setting
0.00000 [mH]