Parameters
Parameter list
r2054
PROFIBUS status / PB status
CU
Can be changed: -
Data type: Integer16
P-Group: Communication
Min
-
Description:
Status display for the PROFIBUS interface.
Values:
0:
1:
2:
3:
4:
Note:
Re r2054 = 3:
In state 3 (the LED flashes green), a cyclic connection has been established to the PROFIBUS master; however,
one of the following prerequisites is missing for cyclic operation:
- No setpoints are being received as the PROFIBUS master is in the STOP condition.
Only for clock-cycle synchronous operation:
- The drive is not in synchronism as the global control (GC) has an error.
- The master sign-of-life (r2050[3], r2093.12-15) is not being correctly received on a drive object SERVO. Possible
causes:
- the sign-of-life is completely missing.
- the sign of life is not incremented in the Tmapc (r2064[2]) cycle.
- the sign-of-life (p2045) has not been correctly interconnected (r2050[3]).
The OK status can be identified on a SERVO drive object if the drive increments the slave sign-of-life (r2053[3].12-
15).
Re r2054 = 4:
In the status 4 (LED green), the cyclic connection to the PROFIBUS master has been established and setpoints are
being received. The clock cycle synchronization is OK - sign-of-life characters are being received and sent at all
SERVO drive objects.
r2055[0...2]
PROFIBUS diagnostics standard / PB diag standard
CU
Can be changed: -
Data type: Unsigned16
P-Group: Communication
Min
-
Description:
Diagnostics display for the PROFIBUS interface.
Index:
[0] = Master bus address
[1] = Master input total length bytes
[2] = Master output total length bytes
1-238
Off
No connection (baud rate search)
Connection O. K. (baud rate found)
Cyclic connection with master (data exchange)
Cyclic data O. K.
Data set: -
Units group: -
Max
-
Data set: -
Units group: -
Max
-
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Access level: 3
Function diagram: 2410
Unit selection: -
Factory setting
-
Access level: 3
Function diagram: 2410
Unit selection: -
Factory setting
-