[0] = AO 0 (X482.5/X482.6)
[1] = AO 1 (X482.7/X482.8)
Note:
The parameters for the characteristic do not limit.
p4078[0...1]
TM31 analog outputs, characteristic value y1 / TM31 AO char y1
TM31
Can be changed: U, T
Data type: Floating Point
P-Group: Terminals
Min
-20.000 [V]
Description:
Sets the normalization characteristic for the analog outputs of terminal module 31 (TM31).
The normalization characteristic for the analog outputs is defined using 2 points.
This parameter specifies the y coordinate (output voltage in V or output current in mA) of the 1st value pair of the
characteristic.
Index:
[0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Dependency:
The units of this parameter (V or mA) depend on the analog input type.
Refer to: p4076
Notice:
This parameter is automatically overwritten when the analog output type is changed (p4076).
Note:
This parameter is automatically overwritten if p4076 (type of analog output) is changed.
The parameters for the characteristic do not limit.
p4079[0...1]
TB30 analog outputs, characteristic value x2 / TB30 AO char x2
TB30
Can be changed: U, T
Data type: Floating Point
P-Group: Terminals
Min
-1000.00 [%]
Description:
Sets the normalization characteristic for the analog outputs of terminal board 30 (TB30).
The normalization characteristic for the analog outputs is defined using 2 points.
This parameter specifies the x coordinate (percentage) of the 2nd value pair of the characteristic.
Index:
[0] = AO 0 (X482.5/X482.6)
[1] = AO 1 (X482.7/X482.8)
Note:
The parameters for the characteristic do not limit.
p4079[0...1]
TM31 analog outputs, characteristic value x2 / TM31 AO char x2
TM31
Can be changed: U, T
Data type: Floating Point
P-Group: Terminals
Min
-1000.00 [%]
Description:
Sets the normalization characteristic for the analog outputs of terminal module 31 (TM31).
The normalization characteristic for the analog outputs is defined using 2 points.
This parameter specifies the x coordinate (percentage) of the 2nd value pair of the characteristic.
Index:
[0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Dependency:
Refer to: p4076
Notice:
This parameter is automatically overwritten when the analog output type is changed (p4076).
Note:
This parameter is overwritten if p4076 (type of analog output) is changed.
The parameters for the characteristic do not limit.
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Data set: -
Units group: VOLTAGE_AC_PP
Max
20.000 [V]
Data set: -
Units group: PERCENT
Max
1000.00 [%]
Data set: -
Units group: PERCENT
Max
1000.00 [%]
Parameters
Parameter list
Access level: 2
Function diagram: 9572
Unit selection: -
Factory setting
0.000 [V]
Access level: 2
Function diagram: 9106
Unit selection: -
Factory setting
100.00 [%]
Access level: 2
Function diagram: 9572
Unit selection: -
Factory setting
100.00 [%]