Siemens SINAMICS G List Manual page 644

Table of Contents

Advertisement

Faults and Alarms
List of faults and alarms
Remedy:
- replace the firmware on the voltage sensing module by an older firmware version (r0xyz).
- upgrade the firmware on the control unit (r0018).
Reaction upon F:
NONE (OFF1, OFF2, OFF3)
Acknowledge
IMMEDIATELY (power on)
upon F:
Reaction upon N:
NONE
Acknowledge
NONE
upon N:
A35200 (F, N)
TM: Calibration data
Reaction:
NONE
Acknowledge:
NONE
Cause:
An error was detected in the calibration data of the terminal module.
Alarm value (r2124, decimal):
The hundred thousands and ten thousands location specifies the component Id of the terminal module where the
fault occurred.
The thousands location specifies whether the analog input 0 (=0) or analog output 1 (= 1) is involved.
The hundreds location specifies the fault type:
0: No calibration data available.
1: Offset too high (> 100 mV).
The tens and ones location specifies the number of the input involved.
Remedy:
Power-down the unit and power-up again.
If the fault is still present, replace the module/board.
Reaction upon F:
NONE
Acknowledge
IMMEDIATELY (power on)
upon F:
Reaction upon N:
NONE
Acknowledge
NONE
upon N:
F35207 (N, A)
TM: Temperature, threshold value exceeded
Reaction:
OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY (power on)
Cause:
The temperature measured using the temperature sensing of the TM (r4105) has exceeded the threshold value to
initiate this fault (p4102[1]).
Please note that this fault can only be initiated if the temperature evaluation was activated (p4100 = 2 for KTY sensor
or p4100 = 1 for PTC sensor).
Fault value (r0949, decimal):
The hundred thousands and ten thousands location specifies the component number of the TMxx where the fault
occurred.
Alarm:
Please note that Fault F35207 only causes the drive to be shut down if there is at least one BICO interconnection
between the drive and TM31.
Remedy:
- allow the temperature sensor to cool down.
- if required, set the fault response to NONE (p2100, p2101).
Reaction upon N:
NONE
Acknowledge
NONE
upon N:
Reaction upon A:
NONE
Acknowledge
NONE
upon A:
A35211 (F, N)
TM: Temperature threshold value exceeded
Reaction:
NONE
Acknowledge:
NONE
3-644