Siemens SINAMICS G List Manual page 581

Table of Contents

Advertisement

Cause:
The monitoring time for the sign-of-life counter has expired.
Remedy:
Check communication line.
Reaction upon A:
NONE
Acknowledge
NONE
upon A:
F08510 (A)
COMM BOARD: send configuration data not valid.
Reaction:
OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
COMM BOARD did not accept the send-configuration data.
Fault value (r0949, decimal):
Return value of the send-configuration data check.
Remedy:
Check the send configuration data.
Reaction upon A:
NONE
Acknowledge
NONE
upon A:
A08511 (F)
COMM BOARD: Receive configuration data not valid
Reaction:
NONE
Acknowledge:
NONE
Cause:
The drive unit did not accept the receive-configuration data.
Alarm value (r2124, decimal):
Return value of the receive-configuration data check.
0: Configuration accepted.
1: Drive overflow.
2: Data length overflow.
3: Data length uneven.
4: Setting data for synchronization not accepted.
5: Drive still not in cyclic operation.
6: Buffer system not accepted.
7: Cyclic channel length too short for this setting.
8: Cyclic channel address not initialized.
9: 3-buffer system not permitted.
10: DRIVE-CLiQ fault.
11: CU link fault.
12: CX32 not in cyclic operation.
Remedy:
Check the receive configuration data.
Reaction upon F:
NONE (OFF1, OFF2, OFF3)
Acknowledge
IMMEDIATELY
upon F:
A08520 (F)
COMM BOARD: Non-cyclic channel error
Reaction:
NONE
Acknowledge:
NONE
Cause:
The memory or the buffer status of the non-cyclic channel has an error.
Alarm value (r2124, decimal):
0: Error in the buffer status.
1: Error in the memory.
Remedy:
Check communication line.
Reaction upon F:
NONE (OFF1, OFF2, OFF3)
Acknowledge
IMMEDIATELY
upon F:
A08530 (F)
COMM BOARD: Message channel error
Reaction:
NONE
Acknowledge:
NONE
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Faults and Alarms
List of faults and alarms
3-581