Siemens SINAMICS G List Manual page 158

Table of Contents

Advertisement

Parameters
Parameter list
p1210
Automatic restart, mode / AR mode
VECTOR
Can be changed: U, T
Data type: Integer16
P-Group: Functions
Min
0
Description:
Sets the automatic restart mode (AR).
Values:
0:
1:
4:
6:
Dependency:
The automatic restart requires an active ON command, e.g. that is available at a digital input.
If, for p1210 = 4, 6 there is no active ON command, then the automatic restart is interrupted.
Refer to: p0840, p0857
Refer to: F30003
Cautiont:
A change is only accepted and made if the state "initialization" (r1214.0) and "wait for alarm" (r1214.1).
For p1210 > 1, the motor is automatically started.
Note:
For brief line supply failures, the motor shaft can still be rotating when restarting. In order to restart while the motor
shaft is still rotating, the "flying restart" function should be activated using p1200.
For p1210 = 4, an automatic restart is only carried-out if only fault F30003 has occurred at the motor module.
For p1210 = 1, fault F07320 is not generated if the one and only acknowledgement attempt was not successful
because there is a permanent fault condition.
p1211
Automatic restart, start attempts / AR start attempts
VECTOR
Can be changed: U, T
Data type: Unsigned16
P-Group: Functions
Min
0
Description:
Sets the absolute number of start attempts for the automatic restart function when any faults are automatically
acknowledged (p1210 = 6).
Dependency:
This parameter setting is active for p1210 = 6.
Refer to: p1210, r1214
Cautiont:
A change is only accepted and made if the state "initialization" (r1214.0) and "wait for alarm" (r1214.1).
Note:
A start attempt begins after the fault has been acknowledged and the line supply voltage is available. The start
attempt is exited if the motor was magnetized and an additional delay time of 1 s has expired.
If a fault occurs between the start of the delay time up to the end of the magnetizing time, then the fault is acknowl-
edged and after the delay time p1212 has expired, a new start attempt is initiated. Fault F07320 is output if the
number of parameterized start attempts has been reached. After a successful start attempt, i.e. a fault/error has not
occurred up to the end of the magnetizing phase, the start counter is again reset. For a fault that has re-occurred -
the parameterized number of start attempts is again available.
p1212
Automatic restart, delay time start attempts / WEA t_wait start
VECTOR
Can be changed: U, T
Data type: Floating Point
P-Group: Functions
Min
0.5 [s]
Description:
Sets the delay time up to restart. The delay time is also effective between two starting attempts.
Dependency:
This parameter setting is active for p1210 = 1, 4, 6.
Refer to: p1210, r1214
Cautiont:
A change is only accepted and made if the state "initialization" (r1214.0) and "wait for alarm" (r1214.1).
1-158
Disables automatic restart
Acknowledges all faults without restarting
Automatic restart after line supply failure, no additional start attempts
Restart after any fault with additional start attempts
Data set: -
Units group: -
Max
6
Data set: -
Units group: -
Max
10
Data set: -
Units group: TIME
Max
600.0 [s]
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Access level: 2
Function diagram: -
Unit selection: -
Factory setting
0
Access level: 3
Function diagram: -
Unit selection: -
Factory setting
3
Access level: 3
Function diagram: -
Unit selection: -
Factory setting
1.0 [s]