Remedy:
One of the following counter-measures can be selected if no faults have occurred in the topology detection itself:
If commissioning was still not completed:
- carry-out a self-commissioning routine (starting from p0009 = 1).
general: Set p0099 to r0098, set p0009 to 0; for existing motor modules, this results in servo drives being automati-
cally generated (refer to p0107).
or to generate servo drives: Set p0097 to 1, set p0009 to 0;
or to generate vector drives: Set p0097 to 2, set p0009 to 0.
or to generate vector drives with a parallel circuit configuration: Set p0097 to 12, set p0009 to 0.
In order to set configurations in p0108, before setting p0009 to 0, it is possible to first set p0009 to 2 and p0108 mod-
ified (the index corresponds to the drive object,also refer to p0107).
If commissioning was already completed:
- re-establish the original connections and re-connect power to the control unit.
- restore the factory setting for the complete equipment (all of the drives) and allow automatic self-commissioning
again.
- change the device parameterization to match the connections (this is only possible using the commissioning soft-
ware).
Notice:
Topology changes, that result in this fault being generated, cannot be accepted by the automatic function in the
device, but must be transferred using the commissioning software and parameter download. The automatic function
in the device only allows constant topology to be used. Otherwise, when the topology is changed, all of the previous
parameter settings are lost and replaced by the factory setting.
See also: r0098
F01360
Topology: Actual topology is illegal
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The detected actual topology is not permissible.
Fault value (r0949, hexadecimal):
Byte 1 (cause):
1: Too many components were detected at the control unit. The maximum permissiblen number of components is
199.
2: The component type of a component is not known. The preliminary component number is in the high word.
Note:
The drive system run-up is stopped. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
Re fault value = 1:
Change the configuration. Connect less than 199 components to the control unit.
Re fault value = 2:
Remove the component with unknown component type.
F01375
Topology: Actual topology duplicate connection between two components
Reaction:
NONE
Acknowledge:
IMMEDIATELY