p1219[0...3]
BI: Immediately close motor holding brake / Close brake
VECTOR (Extended
Can be changed: T
brk)
Data type: Unsigned32
P-Group: Functions
Min
-
Description:
Sets the signal source for an unconditional (immediate) closing of the motor holding brake.
Dependency:
Refer to: p1275
Note:
[0]: Signal, immediately close brake, inversion via p1275.0
[1]: Signal, immediately close brake, inversion via p1275.1
[2]: Signal, immediately close brake
[3]: Signal, immediately close brake - refer to the factory setting
These four signals form an OR logic operation.
p1220
CI: Open motor holding brake, signal source, threshold / Open brake thresh
VECTOR (Extended
Can be changed: T
brk)
Data type: Unsigned32
P-Group: Functions
Min
-
Description:
Sets the signal source for the command "open brake".
Dependency:
Refer to: p1221, r1229, p1277
p1221
Open motor holding brake, threshold / Open brake thresh
VECTOR (Extended
Can be changed: U, T
brk)
Data type: Floating Point
P-Group: Functions
Min
0.00 [%]
Description:
Sets the threshold value for the command "open brake".
Dependency:
Refer to: p1220, r1229, p1277
p1222
BI: Motor holding brake, feedback signal, brake closed / Brake feedb closed
VECTOR (Extended
Can be changed: T
brk)
Data type: Unsigned32
P-Group: Functions
Min
-
Description:
Sets the signal source for the feedback signal "brake closed".
For motor holding brakes with feedback signal, the signal "brake closed" can be activated using p1275.5 = 1.
Dependency:
Refer to: p1223, p1275
Note:
1 signal: Brake closed.
When braking with 1 feedback signal, the inverted feedback signal is connected to the BICO input for the second
feedback signal (p1223).
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Data set: -
Units group: -
Max
-
Data set: -
Units group: -
Max
-
Data set: -
Units group: PERCENT
Max
200.00 [%]
Data set: -
Units group: -
Max
-
Parameters
Parameter list
Access level: 2
Function diagram: 2707
Unit selection: -
Factory setting
[0] 0
[1] 0
[2] 0
[3] 1229.9
Access level: 2
Function diagram: 2707
Unit selection: -
Factory setting
1
Access level: 2
Function diagram: 2707
Unit selection: -
Factory setting
0.00 [%]
Access level: 2