Siemens SINAMICS G List Manual page 280

Table of Contents

Advertisement

Parameters
Parameter list
p2264[0...n]
CI: Technology controller actual value / Tec_ctr act val
VECTOR (Tech ctrl) Can be changed: U, T
Data type: Unsigned32
P-Group: Technology
Min
-
Description:
Sets the signal source for the actual value of the technology controller.
p2265
Technology controller actual value filter time constant / Tec_ctr act T
VECTOR (Tech ctrl) Can be changed: U, T
Data type: Floating Point
P-Group: Technology
Min
0.00 [s]
Description:
Sets the time constant for the actual value filter (PT1) of the technology controller.
r2266
CO: Technology controller actual value after filter / Tec_ctr act a. flt
VECTOR (Tech ctrl) Can be changed: -
Data type: Floating Point
P-Group: Technology
Min
- [%]
Description:
Displays the smoothed actual value after the filter (PT1) of the technology controller
r2273
CO: Technology controller error / Tec_ctr error
VECTOR (Tech ctrl) Can be changed: -
Data type: Floating Point
P-Group: Technology
Min
- [%]
Description:
Displays the error (system deviation) between the setpoint and actual value of the technology controller.
Dependency:
Refer to: p2263
p2274
Technology controller differentiation, time constant / Tec_ctr T diff
VECTOR (Tech ctrl) Can be changed: U, T
Data type: Floating Point
P-Group: Technology
Min
0.000 [s]
Description:
Sets the time constant for the differentiation (D component) of the technology controller.
Note:
p2274 = 0: Differentiation is disabled.
p2280
Technology controller proportional gain / Tec_ctr Kp
VECTOR (Tech ctrl) Can be changed: U, T
Data type: Floating Point
P-Group: Technology
Min
0.000
Description:
Sets the proportional gain (P component) of the technology controller.
1-280
Data set: CDS
Units group: -
Max
-
Data set: -
Units group: TIME
Max
60.00 [s]
Data set: -
Units group: PERCENT
Max
- [%]
Data set: -
Units group: PERCENT
Max
- [%]
Data set: -
Units group: TIME
Max
60.000 [s]
Data set: -
Units group: -
Max
1000.000
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Access level: 2
Function diagram: 7958
Unit selection: -
Factory setting
0
Access level: 2
Function diagram: 7958
Unit selection: -
Factory setting
0.00 [s]
Access level: 2
Function diagram: 7958
Unit selection: -
Factory setting
- [%]
Access level: 2
Function diagram: 7958
Unit selection: -
Factory setting
- [%]
Access level: 2
Function diagram: 7958
Unit selection: -
Factory setting
0.000 [s]
Access level: 2
Function diagram: 7958
Unit selection: -
Factory setting
1.000

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents